9.  A vertical vent must exhaust outside the building at least 3 feet (0.91m) above the point of the exit and at least 2 

feet (0.61 m) above the highest point of the roof within a 10-foot (3.05 m) radius of the termination. 

10.  A vertical termination less than 10 feet (0.91 m) from a parapet wall must be a minimum of 2 feet (0.61 m) higher 

than the parapet wall 

7.3.3  Combining Category III or Category IV Vents 

 

Combined VT3 Category III or Category IV gas vent systems must incorporate an Exhausto, Tjernlund or U.S. Draft 
variable speed, modulating, mechanical draft inducer capable of maintaining the appropriate negative draft at the end 
of the common flue, to assure that all boilers in the combined vent system operate with a negative draft. 

Do not 

exceed negative 0.25” W.C.

 See “Combining Vents with a Draft Inducer

” 

illustration below. 

 

WARNING: Do not connect multiple boiler vents into a single unpowered or fixed speed powered vent. This 
could cause unsafe operation and the potential for poisonous carbon monoxide to enter occupied areas. 
Such improper installation can cause property damage, personal injury, exposure to hazardous materials or 
death. 
 
WARNING: Do not combine appliances utilizing Category I or Category II venting into the same vent system 
with appliances utilizing Category III or Category IV venting. This could cause unsafe operation and the 
potential for poisonous carbon monoxide to enter occupied areas. Such improper installation can cause 
property damage, personal injury, exposure to hazardous materials or death. 

 

 

Conventional Venting 

Through the Wall Venting 

Combining Vents with a Draft Inducer 

 

 

 

 

 
 

OPERATING AND SAFETY CONTROLS 

8.1  Operating Temperature Control  

 

An adjustable digital operating control is located in the front control panel. See TempTrac Electronic Controller Panel 

in this manual for more information. 

8.2  High Water Temperature Limit Control

 

The boiler is equipped with adjustable limit and high limit controls to control the maximum discharge water 
temperature. These controls are located inside the control cabinet and are accessed by removing the bottom cover. 
The High Limit Control is of the manual reset type and may be reset by pressing the limit reset button accessible 
through the control panel cover. The Lower Limit is of the auto reset type and can be dial adjusted to operate just 
above the set point of the main Operating Temperature Control. Pressing the reset on the High Limit Control will not 
cause the control to reset until the water temperature has dropped below the set point of the manual reset High 
Limit Control. 
 

WARNING: Turn off all electrical service to the appliance when accessing the limit or high limit controls 
located inside the control cabinet. This cabinet contains High Voltage wiring and terminals. If the electrical 
service is not turned off and these terminals are touched, a dangerous shock causing personal injury or 
death could occur. Close and fasten the control cabinet cover before restoring electrical service to the 
appliance. 

8.3 Relief 

Valve 

 

A pressure only relief valve(s) sized in accordance with the ASME Boiler and Pressure Vessel Code, Section IV, is 
installed in the tank. 

Summary of Contents for 1500 WB 250A-IF

Page 1: ...LOW THE INFORMATION IN THIS MANUAL AND ALL OTHER PROVIDED INSTRUCTIONS LABELS AND MARKINGS BEFORE INSTALLING OPERATING OR SERVICING THIS UNIT TO THE INSTALLER After installation these instructions mus...

Page 2: ...ection 5 6 Gas Train and Controls Certification 5 7 Gas Control Trains 6 Combustion and Ventilation Air 6 1 Equipment Located In Confined Spaces 6 2 Maximum Allowed Remote Combustion Air Inlet Length...

Page 3: ...mpTrac 10 4 Boiler Management System BMS Remote Connections 10 5 Outdoor Reset 10 6 OnTrac Boiler Management System BMS 10 7 BAS Protocol Gateway 11 Sequence of Operation 12 Initial Startup 12 1 Initi...

Page 4: ...ut the main gas supply valve to the appliance from a location safely away from the emergency Failure to follow these instructions can cause property damage personal injury and exposure to hazardous ma...

Page 5: ...5 34 55 08 14 2 PRODUCT DESCRIPTION Component Controls and Connection Locations Locations May Vary...

Page 6: ...be enclosed in approved conduit or approved metal clad cable To avoid serious damage DO NOT energize the unit until the system and appliance is full of water 3 4 Location These units are suitable for...

Page 7: ...ow pumping systems on the boiler loop motorized isolation valves may be recommended Building flow may have to be limited to only the firing boilers during periods of low building heat demand to preven...

Page 8: ...xchanger can cause a non warrantable failure 3 Make sure there are no system leaks DO NOT use petroleum based stop leak products All system leaks must be repaired The constant addition of make up wate...

Page 9: ...aight Pipe to add the equivalent straight pipe for each elbow or tee to obtain the total distance from the meter Use this corrected total distance from the meter for determining the suggested pipe siz...

Page 10: ...off device 6 A sediment trap drip leg MUST be provided in the inlet of the gas connection to the unit 7 The code compliant vent limiters are designed and must respond to pressure changes in the instal...

Page 11: ...tion Codes or applicable provisions of the local building codes NOTE This unit may be installed with a remote air intake system which uses a make up air duct to draw combustion air directly from outdo...

Page 12: ...remote combustion air vent termination to adequately protect the combustion air inlet from wind and weather A UL Listed air intake termination cap is available from Riverside Hydronics and may have s...

Page 13: ...om the appliance vent connection to the vertical vent or stack that terminates outside and above the building roof must be made with listed Type B double wall or equivalent must be as direct as possib...

Page 14: ...manufacturer of the listed Category III or IV venting system being installed Attach this adapter to the VT3 vent connection outlet following the instruction provided by the adapter s manufacturer Foll...

Page 15: ...e cfm Max Vent Press W C 399 136 0 5 500 170 0 6 650 221 0 8 750 255 1 0 850 289 1 2 900 306 1 2 1000 340 1 3 7 3 2 Vertical or Horizontal Vent Termination 1 The vent terminal must have a minimum clea...

Page 16: ...personal injury exposure to hazardous materials or death Conventional Venting Through the Wall Venting Combining Vents with a Draft Inducer 8 OPERATING AND SAFETY CONTROLS 8 1 Operating Temperature C...

Page 17: ...expansion Contact a boiler or plumbing professional to resolve this situation Do not plug the relief valve 8 4 Electronic Low Water Cut Off Low Water Cut Off Operation When the water level is above th...

Page 18: ...g Probe 1 This is used to regulate the temperature of the boiler 9 4 Control Buttons SET Displays and modifies the temperature set points In programming mode it selects a parameter or confirms an oper...

Page 19: ...will hold at low fire until parameter St4 is reached causing burner to modulate higher or parameter St1 is reached causing the burner to shutoff St4 The Modulation Threshold This additional differenti...

Page 20: ...int Push the SET key The upper display will show the St1 parameter name while the lower display will show its value Use the UP or DOWN key to cycle through the parameter names Push the SET key to modi...

Page 21: ...ted or is reading correctly Outdoor reset disabled Warm weather shutdown disabled Check wiring and sensor Terminals 16 17 HA High temperature limit setpoint exceeded Buzzer sounds operation continues...

Page 22: ...daisy chain arrangement 10 4 Making BMS BAS remote connections for analog and binary on off signals A terminal strip for the remote connection is located behind the hinged control panel at the top of...

Page 23: ...adjusted upward by the amount of the rr1 value See Outdoor Reset Manual 34 400 6 for full description Factory Default Settings The values of the Outdoor Reset and Warm Weather Shutdown functions in th...

Page 24: ...he Fenwal Flame Safeguard Control d 24v is applied to the TempTrac operating temperature control terminal L1 3 Call For Heat If the TempTrac operating control senses a call for heat condition a The Hi...

Page 25: ...lay On Low Fire Hold Relay has timed out it energizes the Modulation Release Relay SPDT to enable the analog signal from the TempTrac to the VFD to regulate the speed of the blower a The TempTrac will...

Page 26: ...Tools 12 2 Resources Product Installation Maintenance Manuals Start up Report with instructions Local State Federal Codes Toll Free 24 Hour Technical Support 1 800 433 5654 12 3 On Site Consideration...

Page 27: ...ng the rocker switch on the front of the control enclosure assembly When the burner fails to light the flame control will lockout Start the burner in Low Fire Burner combustion must be optimized at bo...

Page 28: ...in the flue vent approximately two feet from the appliance See Gas Train Illustration below for details With the burner firing and adjusted to low fire adjust the regulator screw clockwise to increas...

Page 29: ...LATOR VALVE ORIFICE ADJUSTMENT Gas Train Illustration for Centauri Models 250 through 500 REGULATOR ADJUSTMENT HIGH GAS PRESSURE SWITCH DUAL SAFETY SHUTOFF VALVE LOW PRESSURE GAS SWITCH MANIFOLD PRESS...

Page 30: ...for proper blower pressure setting adjust if required Air switch may be defective Blocked Filter Switch Check for 24V at the N C side of the blocked filter switch Replace filter or switch as required...

Page 31: ...31 34 55 08 14 14 REPLACEMENT PARTS REPLACEMENT PARTS...

Page 32: ...32 34 55 08 14 14 1 Control Panel...

Page 33: ...316SS 1 EA 8 102163 PROBE THERMOSTAT DIXELL 18NB NTC 25FT NICKEL BRASS 1 EA 9 104195 PROBE THERMOSTAT DIXELL 18NB NTC 5FT NICKEL BRASS 1 EA 10 116458 RELAY SPST 30A 24V OMRON G7L 1A TUB J CB AC24 N O...

Page 34: ...34 34 55 08 14 14 3 Burner Assembly...

Page 35: ...163 ELL BLACK 90DEG 1 16 2 5973 NIPPLE BLACK 1 4 X 2 17 1 101216 SWITCH PRESSURE HGP G ANTUNES 8101111202 2 20 W 18 1 101201 SWITCH PRESSURE LGP G ANTUNES 8103116202 1 20 W 19 1 SEE BOM NIPPLE BLACK 1...

Page 36: ...n or installer should use the procedures described in item 5 6 below 3 Any sign of soot on the heat exchanger or in the flue indicates the need for a combustion inspection Properly installed and adjus...

Page 37: ...combustion and ventilation air is unobstructed to the appliance 10 When electrical controls are serviced or replaced refer to ELECTRICAL COMPONENT LOCATIONS for identification and location of compone...

Page 38: ...detection system components c Check firing rate control d Check piping and wiring of all interlocks and shutoff valves e Inspect burner components f Check igniter g Test high and low gas pressure inte...

Page 39: ...39 34 55 08 14 NOTES...

Page 40: ...40 34 55 08 14 MODEL NUMBER SERIAL NUMBER INSTALLATION DATE Riverside Hydronics LLC 990 Haltom Road Ft Worth TX 76117 1 800 990 5918 www riversidehydronics com...