background image

 

5

SPECIAL DESIGN APPLICATIONS 

 

The EMBLEM

®

 boiler system, when used in connection with a refrigeration system, must be installed so the chilled 

medium is piped in parallel with the boiler with appropriate valves to prevent the chilled medium from entering the boiler. 

 

The boiler piping system of the EMBLEM

®

 (when connected to heating coils located in air handling units where they may 

be exposed to refrigerated air circulation) must be equipped with flow control valves or other automatic means to prevent 
gravity circulation of the boiler water during the cooling cycle.

 

 

PERFORMANCE DATA 

 

The EMBLEM

® 

boiler system is capable of operating with very low flow rates due to the water buffer contained in the 

EPV

®

 boiler. It is recommended however that when variable speed pumps are applied, the minimum flow rate should be 

sufficient to promote fast accurate response to system demands. 

 

The EMBLEM

®

 boiler system is also capable of operating with very low return temperatures. It is recommended in fact 

the return temperature be as low as possible in order to maximize the efficiency of the system. 

 

MAINTENANCE 

 

See individual boiler Installation & Maintenance manuals for details about product maintenance. 

 

WARNING:  When servicing the controls, use exact, Factory authorized, replacement parts and label all wires 
prior to disconnection. Verify proper operation after servicing. Incorrect parts substitution and wiring errors 
can cause damage, improper operation, fire, carbon monoxide and other unexpected and unsafe conditions 
that could result in fire, injury or death. 

 

HEATING BOILER SYSTEM PIPING: 

 

The design document on the following page illustrates examples of both a primary only and a primary – secondary 
hydronic system for single or multiple boiler systems. This is intended as a general guide for use with the EMBLEM

®

 

systems. There are many other layout combinations which are not shown but could be adopted due to the inherent 
flexibility of the 

EMBLEM

®

 

system.  

 

The 

Primary Only System

 is generally not applied with modern 

PRIMERA

®

 boiler systems, due to the need to maintain 

a constant flow rate through the boiler. The cost saving associated with these system can only be realized with the 
application of a medium to high mass boiler. The use of VFD pumping has improved functionality of primary only 
systems but has further increased the risk to 

PRIMERA

®

 boiler systems. The EMBLEM

®

 is well suited for the primary 

only system. 

 

The 

Primary – Secondary System

 most commonly applied to today due to the desire to control the operational 

conditions of the boiler loop separately from the secondary building loop. This system is also more reliably applied when 
heating systems become too large to adequately maintain the proper flow rates and temperature drops across the 
individual heating zones. 

 

The following recommendation should be considered when designing both systems: 

 

Always attempt to apply reverse return piping method to help equalize water flow and simplify balancing of the 
circuits. 

 

Centrifugal system circulating pumps are shown. Circulating pumps should be electrically interlocked with the 
boiler control circuit. The boiler should not fire unless the circulating pumps are running. In the case of VFD 
pumping some minimums threshold of flow should be established and likewise interlocked with the boiler. 

 

Use balancing valves in the supply lines from each boiler to the pumps in order to help equalize or portion the 
flow through the boilers. 

 

A make-up water meter must be installed in any raw water feed to the system. 

 

A means for introducing chemicals to the system water must be provided. 

 

One expansion tank for multiple boilers is typically sufficient when sized properly. 

  A (BMS) boiler management system with Lead/Lag functionality should be used for systems with multiple 

boilers. 

  When using multiple boilers it is recommended that a motorized flow control valve be used in the inlet and 

controlled by the boiler demand or BMS. 

 
 

 
 

 

Riverside Hydronics

®

, LLC  -  990 Haltom Road  -  Fort Worth, Texas  76117  -  Tel 1-800-990-5918

Summary of Contents for Emblem

Page 1: ...structions must be given to the equipment user or left near the appliance Refer to I M documents 34 50 34 501 and 34 502 for additional important information SPECIAL INSTRUCTIONS TO THE OWNER Retain t...

Page 2: ...res are high the EMBLEM system engages a non condensing boiler to supplement heat output Although non condensing the secondary boiler in the EMBLEM system still operates at relatively high efficiency...

Page 3: ...n from the system water to be heated to the Inlet of the EPV boiler Connect the Outlet to the supply side of the system hot water out of the unit FILLING THE UNIT 1 Fill the system with water To be su...

Page 4: ...1 St1 parameter is the first to be displayed Press the Set key again and adjustment is enabled Use the arrow keys to adjust the set point 1 to the desired system temperature and press the set key agai...

Page 5: ...the inherent flexibility of the EMBLEM system The Primary Only System is generally not applied with modern PRIMERA boiler systems due to the need to maintain a constant flow rate through the boiler Th...

Page 6: ...6 Riverside Hydronics LLC 990 Haltom Road Fort Worth Texas 76117 Tel 1 800 990 5918...

Page 7: ...t always the case Untreated make up water is a leading cause for failures of hat water boilers Provisions must be made for properly introducing metering and treating make up water Below are some consi...

Page 8: ...he E series parameters are divided into 10 minute increments The E1 parameter is Sunday The S series parameters are the ending point for the programmed shift in set point The S series parameters are d...

Page 9: ...1 160 E2 0 0 S2 6 0 Sb2 25 LEAD LAG CONTROL OPTION 2 The lead lag and outdoor reset function is managed by a third party Boiler Management System BMS or building Energy Management System EMS This mann...

Page 10: ...ata Function Code Code of the desired function 0X06 Register Address The address of the first register to be read Set point 1 St1 has a register address of 768 Data The data to write CRC Defines the C...

Reviews: