HeatStation™ CONDENSING WATER BOILER
26
34-1161 05/17
WARNING: Turn off all electrical service to the appliance when accessing the limit or other controls located
inside the control cabinet or inside the burner vestibule inside the top of the appliance. Close and fasten the
control cabinet and burner vestibule cover before restoring electrical service to the appliance. The cabinet
and burner vestibule contain High Voltage wiring and terminals. If the electrical service is not turned off and
these terminals are touched, a dangerous shock causing property damage, personal injury or death could
occur.
9.5 Operating Temperature Control
The water temperature is adjustable through a Touch Screen User Interface located in the front control panel. The
control is factory pre-set at approximately 140
º
F. Boiler Control Panel,
Section 10.1
, in this manual for more
information.
Suivez les instructions dans le manuel d'installation pour modifier la température de l'eau de la chaudière.
9.6 High Water Temperature Limit
The boiler Electronic Operating Control System (EOS) includes a single probe that contains a high water temperature
limit and a completely separate supply water operating sensor. Since both these sensors are in the same location in
the heated water supply, the EOS checks to be sure their output is within a degree or two of each other. If not, or if the
maximum water temperature exceeds 210ºF, the EOS will lockout and the manual reset button on the control panel
must be pressed before the boiler will resume operation.