HeatStation™ CONDENSING WATER BOILER
46
34-1161 05/17
14 INITIAL STARTUP
14.1 Initial Startup Requirements
Installation must be complete prior to performing initial startup; and the startup must be complete prior to placing the
boiler into service. Starting the boiler without proper piping, combustion air, venting or electrical connections or control
settings can be dangerous and may void the product warranty. The following startup instructions must be followed
precisely in order to achieve proper and efficient operation to assure trouble-free service life.
WARNING: Proper startup must be made by a qualified installer or service agency, who must read and follow
the supplied instructions and appliance markings. Failure to complete proper startup before use, tampering
with controls or not following all instructions and markings may damage this equipment, void the warranty
and may result in property damage, personal injury or death.
14.2 Tools and Instrumentation Required
Stack Temperature Gauge.
Stack Draft Gauge.
Electronic Combustion Analyzer.
Two U-tube Manometers or pressure gauges.
AC/DC Multi-meter capable of reading low voltage, including less than a volt AC/DC, OHM, and line voltage.
Amp Meter (0.0
– 10.0 Amp)
Normal Hand Tools.
14.3 Resources
Product Installation & Maintenance Manuals.
Start-up Report with instructions.
Local, State, & Federal Codes.
Website: www.riversidehydronics.com
Technical Support: 800-990-5918
14.4 On Site Considerations
Electrical Supply in accordance with the Nameplate Rating.
Adequate uncontaminated indoor or outdoor combustion air.
Adequate Fuel Supply.
Adequate Boiler Water Supply (30 gpm min flow).
Exhaust Vent that complies with the installation instructions.
Adequate support for vent and remote air piping.
Condensate drainage (refer to Sec 5).
14.5 Pre-Startup Checklist
Before starting the unit, check for adequate electrical service, confirm if any external control wiring connections exist,
confirm heater filled with water, check all plumbing connections for leaks, and ensure the condensate trap is installed
properly and that the gas supply meets the product rating decal requirements as follows:
CHECK ELECTRICAL SERVICE
1. Start by checking the electrical service. The standard electrical service required is a 120 volt, single phase, 60
Hertz power supply that is also electrically grounded. See the appliance rating decal on the front of the unit for
the electrical service requirements for your specific product.
2. Next, shut off the electrical service to the unit and turn the boiler power switch to the OFF position.
3. Remove the large front cover in order to gain access to the burner controls and adjustments as well as the main
control enclosure.
Locate the document packet containing the control circuit fuse and fuse cap. A wiring diagram is also in the
document packet.
Remove the fuse and fuse cap from the packet and install them into the fuse holder on the front of the panel.
Check the back of the digital control display board on the hinged panel to see if a 2-wire, RS-485
communication cable is connected. These wires must be removed to isolate the boiler from the Building