Gas Train Illustration for Model HS
14.7 Potentiometer (Adjusting the Setpoint)
The PIM Ignition Control will continue to operate the Heatstation boiler at a 140 degree internal factory setpoint should
the touch screen control fail, or communication between the two devices is interrupted. This internal setpoint can be
adjusted using the potentiometer to maintain a different operating temperature under these circumstances if desired.
If this scenario occurs, the PIM will revert to the supply sensor (outlet sensor) for temperature regulation.
To Adjust The PIM Potentiometer Setpoint:
1. From the View Menu, press and hold the
HOME
button for 3 seconds to display the SETUP Menu.
2. Using the
NEXT ITEM
or
ITEM BACK
buttons navigate to the
TOOLBOX
menu, then touch the
ENTER
button
to display the
ACCESS
menu.
3. Now press and hold the number 4 button to select the
ADVANCED
setings.
4. Touch the
HOME
button to return to the
TOOLBOX
menu, then use the
NEXT ITEM
or
ITEM BACK
buttons
to
navigate to the
SOURCE
menu.
5. Touch
ENTER
to
enter the source menu and use the
NEXT ITEM
or
ITEM BACK
buttons to navigate to the
OPERATOR
screen to display the potentiometer setpoint.
6. Open the hinged upper panel of the control enclosure and locate the potentiometer on the PIM Ignition Module.
7. Using a small blade screwdriver, manually adjust the PIM Potentiometer to a desired stand-alone setpoint
temperature as you view the adjusted temperature setting in the
OPERATOR
screen.
8. Exit the menu by pressing the
HOME
button.