15 TROUBLESHOOTING PROCEDURE
Before troubleshooting the system, check the following items:
Verify all mechanical and electrical connections are secure and tight.
Verify all system wiring is correct.
Verify there is a proper system ground. The igniter, flame sensor, and ignition module must share a common
ground with the burner.
Nuisance shutdowns are often caused by a poor or erratic ground.
Follow the “Initial Startup” instructions in Section 14 as the first step in any troubleshooting.
Verify that the system is powered and that the thermostat is calling for heat.
If the control displays an error code on the red diagnostic LED, troubleshoot per
Section 11
Alarm Messages
–
Diagnostic Codes.
The LED will flash on for 1/10 second, then off for 2/5 second during a fault condition. The pause between fault
codes is 8 seconds.
If the problem is not addressed in this chapter or, if after performing the suggested actions, the problem persists,
contact Riverside Hydronics Technical Support 1-800-990-5918.