HeatStation™ CONDENSING WATER BOILER
59
34-1161 05/17
k. If the blower must be replaced, remove the nuts that attach the blower to the burner transition to remove the
blower.
l.
Replace any damaged components and reassemble in reverse order. (4-5 ft/lbs).
m. Cycle unit and test to verify all safety and operating controls are properly functioning and the burner top plate
flange is free of leaks.
6. Inspect low water cutoffs and relief valves for proper operation at every six months, or more often if indicated by
inspection.
7. Keep appliance area clear and free from combustible materials, gasoline and other flammable vapors and liquids.
8. Check frequently to be sure the flow of combustion and ventilation air is unobstructed to the appliance.
9. When electrical controls are serviced or replaced, label all connections as they are removed, to know the proper
placement on the replacement part.
10. All replacement parts are available through your Riverside Hydronics Dealer. If you need assistance identifying or
contacting your local dealer, you may contact Riverside Hydronics directly at the address and telephone number
located on the first and last page of this manual.
11. If the appliance is to be shut down for an extended period of time, the primary gas valve and the water supply
should be shut off and the heat exchanger should be drained. When the appliance is returned to service, a thorough
inspection of all utilities and general appliance condition should be conducted.
Burner Attachment Layering Illustration