Page 10/ 24
34-81 10/2013
5. PARAMETERS
All the parameters can be set in:
-
Pr1: immediately accessible menu.
-
Pr2: password protected menu.
Label: The displayed label when using the Keypad.
Range: Indicates the possible values and units that can be set.
Firm Version: Firmware of the TempTrac control can be viewed in the rEL parameter.
Label
Firm
Version Description
Range
X÷Y
From
X
to
Y
Rev 0.3
Level
Rev 0.5
Level
Hex
Modbus
Address
Base 0
Modbus
Command
Address
40000+
St1
0.3 & 0.5
Set
point1
LS1÷US1
Pr1
Pr1
0x300
769
St2
0.3 & 0.5
Set
point2
LS2÷US2
Pr1
Pr1
0x301
770
St3
0.3 & 0.5
Set
point3
LS3÷US3
Pr1
Pr1
0x302
771
St5
0.3 & 0.5
Set
point5
Set
point
3
alternate
‐
20÷70°F
Pr1
Pr1
0x303
772
HY1
0.3 & 0.5
Differential
for
St1
‐
22÷22°F
Pr2
Pr2
0x304
773
LS1
0.3 & 0.5
Minimum
set
point1
‐
40°F÷SET
Pr2
Pr2
0x305
774
US1
0.3 & 0.5
Maximum
set
point1
SET
÷
230°F
Pr2
Pr2
0x306
775
AC1
0.3 & 0.5
Anti
‐
short
cycle
delay
for
output
1
0÷30
min.
Pr2
Pr2
0x307
776
S2c
0.3 & 0.5
Configuration
of
St2:
dependent
on
St1
or
independent
diP;
ind
Pr3
Pr2
0x308
777
HY2
0.3 & 0.5
Differential
for
St2
‐
22÷22°F
Pr2
Pr2
0x309
778
LS2
0.3 & 0.5
Minimum
set
point2
‐
40°F÷St2
Pr2
Pr2
0x30A
779
uS2
0.3 & 0.5
Maximum
set
point2
St2
÷
230°F
Pr2
Pr2
0x30B
780
AC2
0.3 & 0.5
Anti
‐
short
cycle
delay
for
output
2
0÷30
min.
Pr2
Pr2
0x30C
781
S3c
0.3 & 0.5
Configuration
of
St3:
dependent
on
St1
or
independent
diP;
ind
Pr2
Pr2
0x30D
782
HY3
0.3 & 0.5
Differential
for
set
point
3
St3
‐
22÷22°F
Pr2
Pr2
0x30E
783
LS3
0.3 & 0.5
Minimum
set
point
3
St3
‐
40°F÷St3
Pr2
Pr2
0x30F
784
uS3
0.3 & 0.5
Maximum
set
point
3
St3
St3
÷
230°F
Pr2
Pr2
0x310
785
AC3
0.3 & 0.5
Anti
‐
short
cycle
delay
for
output
3
0÷30
min.
Pr2
Pr2
0x311
786
o3P
0.3 & 0.5
Probe
selection
for
output
3
Pb1
/
Pb2
Pr2
Pr2
0x312
787
SSE
0.3 & 0.5
Set
point
shift
for
output
3
enable
disable
No;
Yes
Pr2
Pr2
0x313
788
HY5
0.3 & 0.5
Differential
for
set
point
5
‐
22÷22°F
Pr2
Pr2
0x314
789
Ac5
0.3 & 0.5
Anti
‐
short
cycle
delay
for
output
3
alternate
set
point
0÷30
min.
Pr2
Pr2
0x315
790
AcA
0.3 & 0.5
Time
delay
between
the
St3
to
St5
set
point
shift
0÷15
min.
Pr2
Pr2
0x316
791
ANALOGUE OUTPUT 4÷20mA (output 4)
S4c
0.3 & 0.5
Configuration
of
St4:
dependent
on
St1
or
independent
diP;
ind
Pr3
Pr2
0x317
792
St4
0.3 & 0.5
Analogue
output
set
point
‐
100÷100°F
Pr2
Pr2
0x318
793
SR
0.3 & 0.5
Analogue
output
band
width
‐
100÷100°F
Pr2
Pr2
0x319
794
Th4
0.3 & 0.5
Outlet temperature threshold for forcing to 4ma the
analog output
‐
40°F
÷
230°F
Pr2
Pr2
0x31A
795
HY4
0.3 & 0.5
Differential
for
restart
working
of
analog
output
‐
45
÷
‐
1
°F
Pr2
Pr2
0x31B
796
Ac4
0.3 & 0.5
Anti
‐
short
cycle
delay
for
output
4
0÷30
min.
Pr2
Pr2
0x31C
797
PS4
0.3 & 0.5
Analog
output
percentage
(nu=101)
0÷100,
nu
Pr2
Pr2
0x31D
798
PP4
0.3 & 0.5
Analog
output
percentage
with
fault
probe
1
(nu=101)
0÷100,
nu
Pr3
Pr2
0x31E
799
DYNAMIC RESET
tt
0.3 & 0.5
Outdoor
temperature
threshold
for
dynamic
reset
of
St1
‐
40÷230°F
Pr2
Pr2
0x31F
800
rr2
0.3 & 0.5
Outdoor
temperature
band
width
‐
100÷100°F
Pr2
Pr2
0x320
801
rr1
0.3 & 0.5
Maximum
shift
of
St1
‐
100÷100°F
Pr2
Pr2
0x321
802
tt2
0.3 & 0.5
Outdoor
temperature
threshold
to
open
all
the
loads
‐
40÷230°F
Pr2
Pr2
0x322
803