Page 11/ 24
34-81 10/2013
Label
Firm
Version Description
Range
X÷Y
From
X
to
Y
Rev 0.3
Level
Rev 0.5
Level
Hex
Modbus
Address
Base 0
Modbus
Command
Address
40000+
Ht2
0.3 & 0.5
Differential
for
restart
working
of
controller
‐
45
÷
‐
1
°F
Pr2
Pr2
0x323
804
0.3 & 0.5
DIGITAL INPUTS
i1P
0.3 & 0.5
Digital
input
1
polarity
CL÷OP
Pr3
Pr2
0x324
805
i2P
0.3 & 0.5
Digital
input
2
polarity
CL÷OP
Pr2
Pr2
0x325
806
i2d
0.3 & 0.5
Digital
input
2
alarm
delay
0÷255
min.
Pr3
Pr2
0x326
807
i3P
0.3 & 0.5
Digital
input
3
polarity
CL÷OP
Pr2
Pr2
0x327
808
i3d
0.3 & 0.5
Digital
input
3
alarm
delay
0÷255
min.
Pr3
Pr2
0x328
809
0.3 & 0.5
DISPLAY
cF
0.3 & 0.5
Temperature
measurement
unit
°C
÷
°F
Pr3
Pr2
0x329
810
rES
0.3 & 0.5
Resolution
(integer/decimal
point)
only
for
°C
in
÷
de
Pr3
Pr2
0x32A
811
dS2
0.3
Default
showing
for
display
#2
Top
(red)
Pb2,
Pb3
Pr2
0x32B
812
dS2
0.5
Default
showing
for
display
#2
Top
(red)
Pb3
will
display
yellow
EXT,
Ani
will
display
yellow
Valve/M
Pb1,Pb2,Pb3,AnI
Pr2
0x32B
812
dS1
0.3
Default
showing
for
display
#1
Bottom
(Yellow)
Pb1;
tiM
Pr2
0x32C
813
dS1
0.5
Default
showing
for
display
#1
Bottom
(Yellow)
Pb3
will
display
yellow
EXT,
Ani
will
display
yellow
Valve/M
Pb1,Pb2,Pb3,AnI,
TiM
Pr2
0x32C
813
ALARMS
Alc
0.3 & 0.5
Temperature
alarms
configuration:
dependent
on
St1
or
independent
rE÷Ab
Pr3
Pr2
0x32D
814
ALL
0.3 & 0.5
minimum
temperature
alarm,
referred
to
TP1
‐
40÷230°F
Pr2
Pr2
0x32E
815
Alu
0.3 & 0.5
MAXIMUM
temperature
alarm,
referred
to
TP1
‐
40÷230°F
Pr3
Pr2
0x32F
816
AFH
0.3 & 0.5
Differential
for
temperature
alarm
recovery
1÷45°F
Pr2
Pr2
0x330
817
ALd
0.3 & 0.5
Temperature
alarm
delay
0÷255
min.
Pr2
Pr2
0x331
818
dAo
0.3 & 0.5
Delay
of
temperature
alarm
at
start
up
1
=
10
min
disp
0.1
0
÷
23h
50
min.
Pr2
Pr2
0x332
819
ANALOGUE INPUTS
oF1
0.3 & 0.5
First
probe
calibration
‐
21÷21°F
Pr3
Pr2
0x333
820
P2P
0.3 & 0.5
Second
probe
presence
No;
Yes
Pr2
Pr2
0x334
821
oF2
0.3 & 0.5
Second
probe
calibration
‐
21÷21°F
Pr3
Pr2
0x335
822
P3P
0.3 & 0.5
Third
probe
presence
No;
Yes
Pr2
Pr2
0x336
823
oF3
0.3 & 0.5
Third
probe
calibration
‐
21÷21°F
Pr3
Pr2
0x337
824
TIME AND DATE
Hur
0.3 & 0.5
Current
hour
0
÷
23
Pr2
Pr2
0x338
825
Min
0.3 & 0.5
Current
minute
0
÷
59
Pr2
Pr2
0x339
826
dAY
0.3 & 0.5
Current
day
Sun
÷
SAt
Pr2
Pr2
0x33A
827
ENERGY SAVING TIMES
E1
0.3 & 0.5
Energy
saving
start
on
Sunday
0
÷
23h
50
min.
‐
nu
Pr2
Pr2
0x33B
828
S1
0.3 & 0.5
Energy
saving
stop
on
Sunday
0
÷
23h
50
min.
‐
nu
Pr2
Pr2
0x33C
829
Sb1
0.3 & 0.5
Set
back
temperature
on
Sunday
‐
40÷40°F
Pr2
Pr2
0x33D
830
E2
0.3 & 0.5
Energy
saving
start
on
Monday
0
÷
23h
50
min.
‐
nu
Pr2
Pr2
0x33E
831
S2
0.3 & 0.5
Energy
saving
stop
on
Monday
0
÷
23h
50
min.
‐
nu
Pr2
Pr2
0x33F
832
Sb2
0.3 & 0.5
Set
back
temperature
on
Monday
‐
40÷40°F
Pr2
Pr2
0x340
833
E3
0.3 & 0.5
Energy
saving
start
on
Tuesday
0
÷
23h
50
min.
‐
nu
Pr2
Pr2
0x341
834
S3
0.3 & 0.5
Energy
saving
stop
on
Tuesday
0
÷
23h
50
min.
‐
nu
Pr2
Pr2
0x342
835
Sb3
0.3 & 0.5
Set
back
temperature
on
Tuesday
‐
40÷40°F
Pr2
Pr2
0x343
836
E4
0.3 & 0.5
Energy
saving
start
on
Wednesday
0
÷
23h
50
min.
‐
nu
Pr2
Pr2
0x344
837
S4
0.3 & 0.5
Energy
saving
stop
on
Wednesday
0
÷
23h
50
min.
‐
nu
Pr2
Pr2
0x345
838
Sb4
0.3 & 0.5
Set
back
temperature
on
Wednesday
‐
40÷40°F
Pr2
Pr2
0x346
839
E5
0.3 & 0.5
Energy
saving
start
on
Thursday
0
÷
23h
50
min.
‐
nu
Pr2
Pr2
0x347
840