Page 15/ 24
34-81 10/2013
6.3
OUTPUT 2 2ND STAGE (oS2=Std 2on=rEG)
Kind of action
: Heating
Reference probe
: TP1
Terminals:
SPADE 6 & 7
Related Parameters:
S2c, St2, Hy2, LS2, US2, AC2, oS2, 2on
time
time
Out2
Probe1
Set2
Set2+ Hy2
NOTES
1. Output 2 will function as an output temperature control when
oS2
=
Std
, otherwise output 2 is an alarm output
contact.
2.
S2c
determines if
St2
is relative to
St1
or independent. (
S2c
=
dep
or
ind
).
3.
Hy2
functionality same as
Hy1
. See
OUTPUT 1 CALL FOR HEAT
.
6.4
OUTPUT 2 AS ALARM RELAY (oS2=AL, 2ON=REG)
1. Output 2 will function as an alarm contact when oS2=AL.
2. When an alarm condition occurs, Output 2 will be energized (relay closes) as an indication of an alarm condition.
3.
Terminals:
SPADE 6 & 7.