Page 17/ 24
34-81 10/2013
6.6
OUTPUT 3 ALTERNATE SET POINT
Kind of action
: Heating
Reference probe
: TP1 or TP2
Related Parameters:
St3, Hy3, LS3, US3, AC3, St5, Hy5, 3on, o3P, SSE, AC5, ACA
NOTES
1. When
SSE
is enabled and Output 1 is in a de-energized state (off) Output 3 will function according to
St3
. When
Output 1 is in an energized state Output 3 will function according to
St5
.
2.
ACA
delays the change from
St3
to
St5
.
3.
o3P
selects temperature probe to be referenced by Output 3.
4.
Hy1
,
Hy3
and
Hy5
are active but not shown in this illustration.
Set-Point
Shift
Set 3
Set 1
Set 5
On
Out 3
Off
On
Out 1
Off
Time
Set 3
Set 5
Set 3
Alternate Set Point Control
Set 5
ACA Time
Delay