Page 3/ 24
34-81 10/2013
1. TECHNICAL
DATA
Housing:
Self-extinguishing ABS.
Case:
Facia 100x64 mm; depth 76mm
Mounting:
Panel mounting in a 56x72 mm panel cut-out with two screws.
3x2mm. Distance between the holes
40mm
Protection:
IP20.
Frontal protection:
IP65 with optional frontal gasket mod. RGW-V
Connections:
Spade on connectors 6.3 mm for supply and relays and 4÷20mA-
Screw terminals block for probes, digital input
Power supply:
24Vac Class 2
Power absorption:
7VA max.
Display:
Dual display
Relay outputs:
3 SPST relay contacts, 3A, 8A resistive load.
Other output:
Audible alarm
4÷20mA modulation output
Inputs:
3 NTC probes
Digital inputs:
3 Dry Contact
Hot key facility
for fast programming
Serial output:
TTL standard
Communication protocol:
Modbus - RTU
Data storing:
On non-volatile memory (EEPROM).
Internal clock back-up:
24 hours
Kind of action:
1B.
Pollution grade:
Normal
Software class:
A.
Operating temperature:
32÷140°F
(
0÷60 °C)
Storage temperature:
-13÷140°F
(
-25÷60 °C)
Relative humidity:
20÷85% (no condensing)
Measuring and regulation range: NTC probe:
-58÷230°F
(
-40÷110°C)
Resolution:
1°F or 1 °C (selectable).
Accuracy (ambient temp. 77°F)
: ±1 °F ±1 digit
2. WIRING
DIAGRAMS