2.PROCEDURE FOR SETTING
IMCB10-E1
7
The details of parameters in each initialize code group are described in the following.
2.3 Details of parameters in initialize code 0 (Cod=0)
(1) SL1 (Input type selection)
Conduct the setting so that it matches the instrument specification (input type). If the
setting is changed, always re-set the setting limits (SLH and SLL). (See P.12, 13)
Factory set value varies depending on the input type.
Set value
Input type
0
0
0
0
K
0
0
0
1
J
0
0
1
0
L
0
0
1
1
E
0
1
0
0
N
0
1
1
1
R
1
0
0
0
S
1
0
0
1
B
1
0
1
0
W5Re/W26Re
1
0
1
1
PL II
0
1
0
1
T
0
1
1
0
U
Thermocouple input
(TC)
1
1
0
0
Pt100
Ω
(JIS/IEC)
1
1
0
1
JPt100
Ω
(JIS)
RTD input
1
1
1
0
0 to 5V DC
1
1
1
0
0 to 10V DC
*1
Voltage input
1
1
1
1
1 to 5V DC
1
1
1
0
0 to 20 mA DC
1
1
1
1
4 to 20 mA DC
Current input *2
*1 To be fixed to "1110" for the 0 to 10 V DC (Z-1010 specification). No input type cannot be
changed as the hardware differs.
*2 For the current input specification, a resistor of 250
Ω
must be connected between the input
terminals.
Parameter display position
CAUTION
Measured value (PV) display unit shows parameter No. (character).
Input the numerical value in the set value (SV) display unit.
*Note that the relevant digit used
differs depending on the parameter.
The figure at the above is for selects the "Limit action (low limit)" in "SL6 (Limit action type selection)."
Set value
0
1