2.PROCEDURE FOR SETTING
IMCB10-E1
9
(4) SL4 (Alarm 1 type selection)
Instrument without the alarm 1 (ALM1) is set to "0000."
Factory set value varies depending on the instrument specification.
Set value
Description
0
0
0
Alarm 1 (ALM1) not provided
Alarm 1 (ALM1) type selection
0
0
1
Deviation high alarm
0
1
0
Deviation high/low alarm
0
1
1
Process high alarm
1
0
1
Deviation low alarm
1
1
0
Band alarm
1
1
1
Process low alarm
0
Without alarm hold action
Alarm 1 (ALM1) with hold action
1
With alarm hold action
selection
(5) SL5 (Alarm 2 type selection)
Instrument without the alarm 2 (ALM2) is set to "0000."
Factory set value varies depending on the instrument specification.
Set value
Description
0
0
0
Alarm 2 (ALM2) not provided
Alarm 2 (ALM2) type selection
0
0
1
Deviation high alarm
0
1
0
Deviation high/low alarm
0
1
1
Process high alarm
1
0
1
Deviation low alarm
1
1
0
Band alarm
1
1
1
Process low alarm
0
Without alarm hold action
Alarm 2 (ALM2) with hold action
1
With alarm hold action
selection
CAUTION
CAUTION