2.PROCEDURE FOR SETTING
IMCB10-E1
10
(6) SL6 (Limit action type selection)
The units digit is not used. As malfunction may result, do not change this digit.
Factory set value : "0000"
Set value
Description
0
Fixed
0
Limit action output turned ON at the time of power
Selects the limit
1
Limit actin output turned OFF at the time of power ON action type and
0
Limit action (high limit)
hold action
1
Limit action (low limit)
0
Without alarm hold action
1
With alarm hold action
(7) SL7 (Special specification selection 1)
Instrument without the alarm 1 (ALM1) and alarm 2 (ALM2) is set to "0000".
y
Instrument without the alarm 1 (ALM1). [SL4 setting details : For "0000"]
y
Instrument without the alarm 2 (ALM2). [SL5 setting details : For "0000"]
Factory set value : "1100"
Set value
Description
0
Energize alarm
Energize alarm/de-energize
1
De-energize alarm
selection (Alarm 1 side)
0
Energize alarm
Energize alarm/de-energize
1
De-energize alarm
selection (Alarm 2 side)
0
Z-124 specification not provided
*1
Special specification selection
1
Z-124 specification provided
*2
(Alarm 1 side)
0
Z-124 specification not provided
*1
Special specification selection
1
Z-124 specification provided
*2
(Alarm 2 side)
*1 : The alarm output is forcibly turned ON when the burnout function is activated.
*2 : No alarm action is taken by the burnout function. (Same as the normal alarm action)
CAUTION
CAUTION