2.PROCEDURE FOR SETTING
IMCB10-E1
13
(2) SLL (Setting limiter [low limit] )
z
Set the limiter by referring to "Input range table." (P.15)
z
Limiter setting becomes SLH SLL.
Setting method
Press the <RST key to move the digit, then enter the low limit value of input range by pressing the
UP or DOWN key.
The set value (SV) display unit shows the numeric value.
Factory set value varies depending on the instrument specification.
Input type
Setting range
K
0 to 1372
°
C (0 to 2502
°
F)
J
0 to 1200
°
C (0 to 2192
°
F)
R
0 to 1769
°
C (0 to 3216
°
F)
S
0 to 1769
°
C (0 to 3216
°
F)
B
0 to 1820
°
C (0 to 3308
°
F)
E
0 to 1000
°
C (0 to 1832
°
F)
N
0 to 1300
°
C (0 to 2372
°
F)
T
-199.9 to +400.0
°
C (-199.9 to +752.0
°
F)
W5Re/W26Re
0 to 2320
°
C (0 to 4208
°
F)
PL II
0 to 1390
°
C (0 to 2534
°
F)
U
-199.9 to +600.0
°
C (-199.9 to +999.9
°
F)
Thermocouple
input (TC)
L
0 to 900
°
C (0 to 1652
°
F)
Pt100
Ω
(JIS/IEC)
*1
-199.9 to +649.0
°
C (-199.9 to +999.9
°
F)
RTD input
JPt100
Ω
(JIS)
-199.9 to +649.0
°
C (-199.9 to +999.9
°
F)
0 to 5 V DC
-1999 to +9999
Voltage input
0 to 10 V DC
*2
(programmable scale)
1 to 5 V DC
0 to 20 mA DC
*3
Current input
4 to 20 mA DC
*3
-1999 to +9999
(programmable scale)
*1 : IEC (International Electrotechnical Commission) is equivalent to JIS, DIN and ANSI.
*2 : For the 0 to 10 V DC (Z-1010 specification), no input type cannot be changed as the hardware
differs.
*3 : For the current input specification, a resistor of 250
Ω
must be connected between the input
terminals.