3.COMMUNICATION INITIALIZE IDENTIFIER
IMCB10-E1
20
Name
ID
Data range
#
R/W
Setting limiter (high limit)
[SLH]
XV See "
Input range table
"
(P.14, 15, 16)
To vary
depending on
the shipment
R/W
Setting limiter (low limit)
[SLL]
XW
Setting the position of decimal point
[PGdP]
XU 0 : No digit below decimal point
1 : 1 digit below decimal point
2 : 2 digits below decimal point
3 : 3 digits below decimal point
1
R/W
Differential gap setting of alarm 1
(ALM1)
[AH1]
HA Temperature input :
0 to 100 or 0.0 to 100.0
°
C [
°
F]
Voltage/current input :
0.0 to 10.0
%
of span
See *7
R/W
Differential gap setting of alarm 2
(ALM2)
[AH2]
HB
Holding peak ambient temperature
[TCJ]
Hp
-10 to +100
°
C
0
RO
Operating time display unit (Upper digits)
[WTH]
UT 0 to 10
0
RO
Operating time display unit (Lower digits)
[WTL]
UU 0 to 9999
0
RO
ID
: Identifier
#
: Factory set value
*1
⋅⋅⋅⋅
List of input type selection
Input type
Setting range
Set value
K
0 to 1372
°
C (0 to 2502
°
F)
0
J
0 to 1200
°
C (0 to 2192
°
F)
1
L
0 to 900
°
C
(0 to 1652
°
F)
2
E
0 to 1000
°
C (0 to 1832
°
F)
3
N
0 to 1300
°
C (0 to 2372
°
F)
4
T
-199.9 to +400.0
°
C (-199.9 to +752.0
°
F)
5
U
-199.9 to +600.0
°
C (-199.9 to +999.9
°
F)
6
R
0 to 1769
°
C (0 to 3216
°
F)
7
S
0 to 1769
°
C (0 to 3216
°
F)
8
B
0 to 1820
°
C (0 to 3308
°
F)
9
W5Re/W26Re
0 to 2320
°
C (0 to 4208
°
F)
10
Thermocouple
input (TC)
PL II
0 to 1390
°
C (0 to 2534
°
F)
11