3.COMMUNICATION INITIALIZE IDENTIFIER
IMCB10-E1
21
Input type
Setting range
Set value
Pt100
Ω
(JIS/IEC)
-199.9 to +649.0
°
C (-199.9 to +99.9
°
F)
12
RTD input
(RTD)
JPt100
Ω
(JIS)
-199.9 to +649.0
°
C (-199.9 to +999.9
°
F)
13
0 to 5V DC
0.0 to 100.0 %
14
Voltage input
1 to 5V DC
0.0 to 100.0 %
15
Current input
0 to 20 mA DC
0.0 to 100.0 %
14
*2
⋅⋅⋅⋅
0 : The reset action can be taken and all data items can be cleared in any case where PV, peak
hold value, or over time is displayed.
1 : The reset action can be taken and over time can be cleared only when PV or over time is
displayed. The peak hold value can be cleared only when it is displayed.
2 : The reset action can be taken and peak hold can be cleared only when PV or peak hold is
displayed. Over time can be cleared only when it is displayed.
3 : The reset action can be taken only when PV is displayed. The peak hold value can be
cleared only when it is displayed. Over time can be cleared only when it is displayed.
*3
⋅⋅⋅⋅
0 : No alarm
7 : Process low alarm
1 : Deviation high alarm
9 : Deviation high alarm with hold action
2 : Deviation high/low alarm
10 : Deviation high/low alarm with hold action
3 : Process high alarm
11 : Process high alarm with hold action
5 : Deviation low alarm
13 : Deviation low alarm with hold action
6 : Band alarm
15 : Process low alarm with hold action
*Do not set 4, 8, 12 or 14. Malfunction may result.
*4
⋅⋅⋅⋅
0 : Limit action [high limit] (Limit action output turned ON at the time of power ON)
2 : Limit action [high limit] (Limit action output turned ON at the time of power OFF)
4 : Limit action [low limit] (Limit action output turned ON at the time of power ON)
6 : Limit action [low limit] (Limit action output turned ON at the time of power OFF)
8 : Limit action [high limit] with hold action
(Limit action output turned ON at the time of power ON)
10 : Limit action [high limit] with hold action
(Limit action output turned ON at the time of power OFF)
12 : Limit action [low limit] with hold action
(Limit action output turned ON at the time of power ON)
14 : Limit action [low limit] with hold action
(Limit action output turned ON at the time of power OFF)
*Do not set 1, 3, 5, 7, 9,11 or 13. Malfunction may result.