8. ENGINEERING MODE
IMR01N12-E7
89
Action at input error (high) (1. AoVE, 2. AoVE)
Use to select the action when the measured value reaches the Input error determination point (high).
Data range:
0: Normal control
1: Manipulated output value at input error (PSM)
Factory set value:
Input 1_action at input error (high) (1. AoVE): 0
Input 2_action at input error (high) (2. AoVE): 0
Related parameters:
Input error determination point (high) (P. 70),
Manipulated output value at input error (P. 90)
Input Error Determination:
Example: Input range:
0.0 to 250.0 MPa
Input error determination point (high): 240.0 MPa
Input error determination point (low):
5.0 MPa
Action area at input error
Action area at
input error
Differential gap
(0.1 % of input span)
Input error determination
point (high)
Input range
0.0 MPa
5.0 MPa
240.0 MPa
Manipulated output
value at input error
250.0 MPa
Select one of
these
Manipulated output value
(MV)
obtained by PID control
PID control output
(Within input scale range)
Input error determination point
(low)
Manipulated output
value at input error
Select one of
these
PID control output
Action at input error (low) (1. AUnE, 2. AUnE)
Use to select the action when the measured value reaches the Input error determination point (low).
Data range:
0: Normal control
1: Manipulated output value at input error (PSM)
Factory set value:
Input 1_action at input error (low) (1. AUnE): 0
Input 2_action at input error (low) (2. AUnE): 0
Related parameters:
Input error determination point (low) (P. 71),
Manipulated output value at input error (P. 90)
Description of function:
Refer to
Action at input error (high)
.