9. OPERATION
IMR01N12-E7
102
9.3 Monitoring Display in Operation
In SV setting & Monitor mode, the following operations are possible.
Change the Set value (SV)
Change Memory area
Monitor the Measured value (PV) and the Manipulated value (MV), etc.
Use this mode during normal operation.
Display Sequence
When the Setting change rate limiter is set and the SV is changed, the SV changes
at specific rates in the display.
Continued on the next page.
Input 1_measured value (PV1)/set value (SV1) monitor
Measured value 1 (PV1)
Set value 1 (SV1)
One of set value, Input 1_manipulated output value (MV1) or remote set value can be displayed.
Local state:
The set value is displayed.
Remote state:
The remote set value is displayed.
Manual operation: The Manipulated output value (MV1) of Input 1 can be set.
Setting range: Input 1_output limiter low to Input 1_output limiter high
An MV scaling value (motor RPM) is displayed in the monitor state.
It is also possible to manually charge the MV scaling value.
Display range:
MV scaling low to MV scaling high
SET key
Power ON
Parameter setting mode, Setup setting mode, Operation mode, Engineering mode
Press the shift key while pressing the SET key.
: Parameters related to multi-memory area function
: Parameters displayed when function is specified.
A
AREA
PV1
MAN
MV scaling function
Scaling of an Input 1_manipulated output value (MV1) is conducted in
Engineering mode.
F10_Decimal point position of MV scaling (MVdP)
F10_MV scaling low (MVLS)
F10_MV scaling high (MVHS)
Example: When scaling of an input 1_manipulated output value (MV1) is conducted to
obtain the number of motor revolutions from 0.0 to 80.0 rpm
MAN
AREA
MAN
AREA
OUT1
Keep pressing the UP key until a
value of 60.0 is attained.
MAN
AREA
OUT1
PV1
MAN lamp ON
Decimal point position of MV scaling:
One decimal place
Input 1_MV scaling low (MV1
0.0 %):
0.0 rpm
Input 1_MV scaling high (MV1
100.0 %): 80.0 rpm
Displays any value obtained after scaling of a Manipulated
output value (MV1).
In addition, any value obtained after scaling of a Manipulated output value (MV1)
can be changed.
The number of motor revolutions is increased from 50.0 to 60.0 rpm.