9. OPERATION
IMR01N12-E7
106
Continued from the previous page.
Inerlock function:
The Interlock action holds the event state even if the measured value is out of the event zone
after it enters the event zone once.
Continued on the next page.
Displays the interlock status. Displayed only when the hold interlock is provided. Interlock
status is release when the UP and DOWN keys a simultaneously pressed.
on:
Interlock
off:
Interlock release
Input 1_manipulated output value (MV1) of 0 to 100 % is displayed as a value which is made
scaling to the motor RPM.
Display range:
MV scaling low to MV scaling high
Related parameters:
Decimal point position of MV scaling (P. 64),
MV scaling low (P. 64), MV scaling high (P. 65)
When at a high MV scaling limit value of 100.0 and at a low MV scaling limit value of
0.0, MV1 is displayed.
When set to “high MV scaling limit value = low MV scaling limit value”, the zero
value is displayed.
OUT1
MAN
D
SET key
Input 1_manipulated output value (MV1) monitor
E
OUT1
MAN
Input 2_manipulated output value (MV2) monitor
Displays Input 2_manipulated output value (MV2).
Displayed only when the Input 2_manipulated output value (MV2) function is provided.
Display range:
5.0 to
105.0 %
SET key
"o" corresponding to each Event is lit when the event is turned ON.
Event 1 (EV1)
Event 2 (EV2)
Event 3 (EV3) or Control loop break alarm 1 (LBA1)
Event 4 (EV4) or Control loop break alarm 2 (LBA2)
Event monitor
SET key
Interlock release
SET key
: Parameters related to multi-memory area function
: Parameters displayed when function is specified.