APPENDIX
IMR01N12-E7
A-
13
Function block F30: Output
Name Parameter Data
range
Factory set
value
User set
value
Page
Output logic selection
(LoGC)
1 to 11
(Refer to the following table.)
1, 2, 9 and 10: Unused
1-input: 3
2-input: 5
P.
76
Output 1 timer setting
(oTT1)
0.0 to 600.0 seconds
0.0
P. 77
Output 2 timer setting
(oTT2)
0.0
P.
77
Output 3 timer setting
(oTT3)
0.0
P.
77
Output 4 timer setting
(oTT4)
0.0
P.
77
Output 5 timer setting
(oTT5)
0.0
P.
77
Alarm lamp lighting
condition setting
(ALC1)
SV ten thousand digits:
“0”
Fixed
SV thousands digits: 0 or 1 (Event 4)
SV hundreds digits: 0 or 1 (Event 3)
SV tens digits:
0 or 1 (Event 2)
SV units digits:
0 or 1 (Event 1)
01111
0: ALM lamp isn’t
lit
1: ALM lamp is lit
P.
77
Unused *
(ALC2)
00011
Interlock function
(oTIL)
SV ten thousands digits:
0 or 1 (OUT5)
SV thousands digits: 0 or 1 (OUT4)
SV hundreds digits: 0 or 1 (OUT3)
SV tens digits
0 or 1 (OUT2)
SV units digits:
0 or 1 (OUT1)
00000
0: Unused
1: Used
P.
78
* This item is not used for the HA430/930.
Output logic selection
Set value
OUT1
OUT2 OUT3 OUT4 OUT5
1
This set value is not used for the HA430/930.
2
This set value is not used for the HA430/930.
3
MV1
EV3 or EV4
(Energized)
EV2
(Energized)
EV1
(Energized)
FAIL
(De-energized)
4
MV1
EV3 or EV4
(De-energized)
EV2
(De-energized)
EV1
(De-energized)
FAIL
(De-energized)
5
MV1 MV2 EV4
(Energized)
EV3
(Energized)
EV1 or EV2
(Energized)
6
MV1 MV2 EV4
(De-energized)
EV3
(De-energized)
EV1 or EV2
(De-energized)
7
MV1
MV2
EV3 or EV4
(Energized)
EV2
(Energized)
EV1
(Energized)
8
MV1
MV2
EV3 or 4
(De-energized)
EV2
(De-energized)
EV1
(De-energized)
9
This set value is not used for the HA430/930.
10
This set value is not used for the HA430/930.
11
MV1 EV4
(Energized)
EV3
(Energized)
EV2
(Energized)
EV1
(Energized)