APPENDIX
A-
IMR01N12-E7
18
Continued from the previous page.
Name Parameter Data
range
Factory set
value
User set
value
Page
Event 2 action at input error
(EEo2)
0: Normal
processing
1: Turn the event output ON
0
P.
84
Event 2 assignment
(EVA2)
1: For Input 1
2: For Input 2
1
P.
84
Function block F43: Event 3
Name Parameter Data
range
Factory set
value
User set
value
Page
Event 3 type selection
(ES3)
0: None
1: Deviation
high
2: Deviation
low
3: Deviation
high/low
4: Band
5: Process
high
6: Process
low
7: SV
high
8: SV
low
9: Control loop break (LBA)
0
P.
80
Event 3 hold action
(EHo3)
0: OFF
1: ON
2: Re-hold action ON
0
P.
82
Event 3 differential gap
(EH3)
0 to Input span
(Varies with the setting of the
Decimal point position)
Pressure sensor
input: 2.0 MPa
TC/RTD:
2.0
C [
F]
V/I: 0.2 % of
input
span
P.
83
Event 3 action at input error
(EEo3)
0: Normal
processing
1: Turn the event output ON
0
P.
84
Event 3 assignment
(EVA3)
1: For Input 1
2: For Input 2
1
P.
84