APPENDIX
A-20
IMR01N12-E7
Function block F51: Control 1
Name Parameter Data
range
Factory set
value
User set
value
Page
Input 1_control action type
selection
(1. oS)
0: Direct
action
1: Reverse
action
1
P.
87
Input 1_
integral/derivative time
decimal point position
selection
(1.I ddP)
0: No decimal place
1: One decimal place
2: Two decimal places
2
P.
87
Input 1_derivative gain
(1. dGA)
0.1 to 10.0
6.0
P. 87
Input 1_ON/OFF action
differential gap (upper)
(1. oHH)
0 to Input span
(Varies with the setting of the
Decimal point position)
Pressure sensor
input: 1.0 MPa
V/I: 0.1 % of
input
span
P.
88
Input 1_ON/OFF action
differential gap (lower)
(1. oHL)
Pressure
sensor
input: 1.0 MPa
V/I: 0.1 % of
input
span
P.
88
Input 1_action at input error
(high)
(1.AoVE)
0: Normal
control
1: Manipulated output value
at input error
0
P.
89
Input 1_action at input error
(low)
(1.AUnE)
0
P.
89
Input 1_manipulated output
value at input error
(1. PSM)
5.0 to
105.0 %
5.0
P.
90
Input 1_manipulated output
value when transferred to
Auto from Manual
(1. PSM
)
5.0 to
105.0 %
P.
90
Input 1_output change rate
limiter (up)
(1. orU)
0.0 to 1000.0 %/second of
manipulated output
(0.0: Unused)
0.0
P.
90
Input 1_output change rate
limiter (down)
(1. ord)
0.0
P.
91
Input 1_output limiter high
(1. oLH)
Input 1_output limiter low to
105.0 %
105.0
P.
92
Input 1_output limiter low
(1. oLL)
5.0 % to
Input 1_output limiter high
5.0
P.
92
Unused *
(1. PFF)
0 or 1
Unused *
(1.PFFS)
1.00
Input 1_MV transfer function
(1.MVTS)
0: Unused
1: Used
0
P.
92
* These items are not used for the HA430/930.