6. PARAMETER SETTING MODE
38
IMR01N12-E7
Control response parameter (1. rPT, 2. rPT)
The control response for the Set value (SV) change can be selected among Slow, Medium, and Fast.
Data range:
0: Slow
1: Medium
2: Fast
Factory set value:
Input 1_control response parameter (1. rPT): 0
Input 2_control response parameter (2. rPT): 0
Control Response:
The control response for the Set value (SV) change can be selected among Slow, Medium,
and Fast. If a fast response is required, Fast is chosen. Fast may cause overshoot. If
overshoot is critical, Slow is chosen.
Measured value (PV)
Set value
(SV2)
Change
Set value (SV) change point
Time
Fast
Medium
Slow
Set value
(SV1)
Setting change rate limiter (up) (1.SVrU, 2.SVrU)
This function is to allow the Set value (SV) to be automatically changed at specific rates when a new Set value
(SV). SVrU is used when the SV is changed to a higher SV.
Data range:
OFF (Unused)
0.1 to Input span/unit time
(Varies with the setting of the Decimal point position)
Factory set value:
Input 1_setting change rate limiter (up) (1.SVrU): OFF
Input 2_setting change rate limiter (up) (2.SVrU): OFF
The unit time can be changed by the Setting change rate limiter unit time in the Engineering mode
(P. 97). (Factory set value: 60 seconds)