8. ENGINEERING MODE
IMR01N12-E7
59
Continued from the previous page.
Mode Description
Default value
Pressure
sensor
input
TC input
RTD input
Voltage/
current
input
Transmission output 1 scale low
Measured value (PV) and Set value (SV): Input scale low
Manipulated output value (MV): 0.0
Deviation:
Input span
Engineering
Transmission output 2 scale low
mode
Transmission output 3 scale low
Event 1 hold action
0 (Without hold action)
Event 2 hold action
Event 3 hold action
Event 4 hold action
Event 1 differential gap
2.0 MPa
2.0
C [
F]
0.2 % of
input span
Event 2 differential gap
Event 3 differential gap
Event 4 differential gap
ON/OFF action differential gap (upper)
1.0 MPa
1.0
C [
F]
0.1 % of
input span
ON/OFF action differential gap (lower)
AT
bias
0
Setting limiter high
Input scale high
Setting limiter low
Input scale low
Setup setting
PV bias
0
mode
PV ratio
1.000
PV low input cut-off
0.00 %
Event 1 set value
50
Event 2 set value
Event 3 set value
Event 4 set value
Control loop break alarm1 (LBA1) time
480 seconds
Parameter
Control loop break alarm2 (LBA2) time
setting
LBA1 deadband
0.0
mode
LBA2 deadband
Proportional
band
30
Integral
time
240.0 seconds
Derivative
time
60.0 seconds
Control response parameter
0 (Slow)
Setting change rate limiter (up)
OFF (Unused)
Setting change rate limiter (down)
SV setting &
Monitor mode
Set value (SV)
0.0 MPa
0.0
C [
F] 0.0
%