8. ENGINEERING MODE
IMR01N12-E7
65
MV scaling low (MVLS)
This value is to set the low limit value of MV scaling monitor value. Set the motor RPM when MV1 = 0 %.
Data range:
1999
.
9 to
9999.9
Factory set value:
0.0
Related parameters:
Decimal point position of MV scaling (P. 64), MV scaling high (P. 64)
MV scaling monitor value is displayed on the SV of PV1/SV1 monitor screen (P. 102).
[Example] If the motor RPM is set to 80.0 rpm when MV1 = 100 %.
Decimal point position of MV scaling:
One decimal place
Input 1_MV scaling low (MV1
0.0 %):
0.0 rpm
Input 1_MV scaling high (MV1
100.0 %): 80.0 rpm
8.5 Direct Key (F11)
Auto/Manual transfer key operation selection
(Fn1)
Use to select Use/Unuse of Auto/Manual transfer key (A/M).
Data range:
0:
Unused
1: Auto/Manual transfer for Input 1
2: Auto/Manual transfer for Input 2
3: Common Auto/Manual transfer for Input 1 and Input 2
Factory set value:
3
Remote/Local transfer key operation selection (Fn2)
Use to select Use/Unuse of Remote/Local transfer key (R/L).
Data range:
0:
Unused
1: Remote/Local transfer
Factory set value:
1
RUN/STOP transfer key operation selection (Fn3)
Use to select Use/Unuse of RUN/STOP transfer key (R/S).
Data range:
0:
Unused
1: RUN/STOP transfer
Factory set value:
1
Display (motor RPM)
80.0 rpm
0.0 rpm
0.0 %
100.0 %
MV1