8. ENGINEERING MODE
IMR01N12-E7
73
8.7 Event Input (F23)
Event input logic selection (dISL)
Use to assign the function (memory area, operation mode) for the Event inputs (DI 1 to DI 5).
Data range:
0 to 15 (Refer to the following table)
[Function Assignment Table]
Set
value
DI 1
DI 2
DI 3
DI 4
DI 5
Terminal
No. 30-31
Terminal
No. 30-32
Terminal
No. 30-33
Terminal
No. 30-34
Terminal
No. 35-36
0
Unused (No function assignment)
1
Memory area number selection (1 to 16)
Memory area set
2
Memory area number selection (1 to 16)
Memory area set
3
Memory area number selection (1 to 16)
Memory area set
4
Memory area number selection (1 to 8)
Memory area set
RUN/STOP transfer
5
Memory area number selection (1 to 8)
Memory area set
Remote/Local transfer
6
Memory area number selection (1 to 8)
Memory area set
Auto/Manual transfer
7
Memory area number selection (1 to 8)
Memory area set
Hold reset
8
Memory area number selection (1 to 8)
Memory area set
Interlock release
9
Memory area number selection (1 to 4)
Memory area set
RUN/STOP transfer
Auto/Manual transfer
10
Memory area number selection (1 to 4)
Memory area set
RUN/STOP transfer
Remote/Local transfer
11
Memory area number selection (1 to 4)
Memory area set
Remote/Local transfer
Auto/Manual transfer
12
Memory area number selection (1 to 4)
Memory area set
Hold reset
Interlock release
13
Auto/Manual transfer
RUN/STOP transfer
Remote/Local transfer
Hold reset
Interlock release
14
Auto/Manual transfer
Input 1_
manual output down
(motor RPM down)
Input 1_
manual output up
(motor RPM up)
Input 1_
manual output 0 % reset
(motor RPM reset)
RUN/STOP transfer
15
Auto/Manual transfer
Input 2_
manual output down
(motor RPM down)
Input 2_
manual output up
(motor RPM up)
Input 2_
manual output 0 % reset
(motor RPM reset)
RUN/STOP transfer
Event input terminals:
Factory set value:
1
Event Input function:
Refer to the next page.
Continued on the next page.
Dry contact input
DI1
31
30
32
33
35
34
36
DI2
DI3
DI4
DI5
COM
COM
Contact input from external devices or equipment should be dry
contact input. If it is not dry contact input, the input should have
meet the specifications below.
Contact specifications: At OFF (contact open) 500 k
or more
At ON (contact closed) 10
or less