8. ENGINEERING MODE
IMR01N12-E7
77
Output timer setting (oTT1 to oTT5)
Output timer setting is to set an output delay time for event outputs.
Data range:
0.0 to 600.0 seconds
Factory set value:
0.0
Related parameters:
Output logic selection (P. 76), Alarm lamp lighting condition setting (P. 77),
Event type selection (P. 80)
Output Timer Setting function:
When an event condition becomes ON status, the output is suppressed until the Output
Timer set time elapses. After the time is up, if the event output is still ON status, the
output will be produced.
Example: When set the event timer to 100.0 seconds.
Non-event state
Event timer
setting time
(100.0 seconds)
Event output ON
Set value (SV)
Event set value
Measured value (PV)
Event timer
setting time
(100.0 seconds)
Event state
Event output OFF
Alarm lamp lighting condition setting (ALC1, ALC2)
Use to set an alarm (ALM) lamp lighting conditions to Event 1 to Event 4.
Data range:
[ALC1 screen]
[ALC2 screen]
(1) Event 1
(6)
As this screen is not used for
0: ALM lamp is not lit 1: ALM lamp is lit
the HA430/930, do not change
(2) Event 2
the setting.
0: ALM lamp is not lit 1: ALM lamp is lit
(3) Event 3
0: ALM lamp is not lit 1: ALM lamp is lit
(4) Event 4
0: ALM lamp is not lit 1: ALM lamp is lit
(5)
“
0” fixed (No setting)
Factory set value:
Event 1 to
Event 4: 1 (ALM lamp is lit)
Related parameters:
Output logic selection (P. 76), Output timer setting (P. 77),
Event type selection (P. 80)
The alarm lamp is lit through the OR operation of Event 1 to Event 4 each of which is set to
“1: ALM lamp is lit.”
(1)
(2)
(3)
(4)
(5)
(6)