IMR01H01-E4

10

5.5 Parameter Setting Mode

The parameter setting mode is used to set various settings relating to control, to change various alarm settings and also to set the setting

change rate limiter and used/unused channels. Setting items belonging to the parameter setting mode correspond to the multi-memory

area functions and can be stored up to eight memories. Press the SET key for 2 seconds with state of PV/SV monitor mode, SV setting &

CT monitor mode, or setup setting mode to shift to this mode. The UP, DOWN or <R/S key is used to change the numeric value, and the

SET key is used to change the parameter as well as to register the numeric value.

!"

Description of each parameter

Control loop break alarm (LBA)

Monitors measured value variations and also sets the time to detect any abnormal control loop.
Displayed only for when the LBA is selected as alarm 1.
Setting range:

0.1 to 200.0 minutes

OFF: LBA function OFF

Factory set value: 8.0 minutes

• 

No setting can be changed when “1 (Lock)” is selected by the lock level 1.

• 

We recommend that the set value of LBA be twice the value of the integral time (I).
If the autotuning function is used, the LBA setting time twice as large as the integral time is
automatically set.

Control loop break alarm deadband (LBD)

Set the area of not outputting LBA. Displayed only for when the LBA is selected as alarm 1.
Setting range:

0 to span (0: LBD OFF)

Factory set value:  Temperature input    0 

°

C [

°

F] or 0.0 

°

C [

°

F]

Voltage input  0.0 %

• 

No setting can be changed when “1 (Lock)” is selected by the lock level 1.

Alarm 1 (ALM1)

Set the ALM1 set value. Displayed when any one of the deviation, process and SV alarms is
selected as the alarm 1.
Setting range:

Process alarm, SV alarm: Same as input range
Deviation alarm: 

-span to +span (Within -1999 to +9999 digits)

Factory set value: Temperature input    50 

°

C [

°

F] or 50.0 

°

C [

°

F]

Voltage input  5.0 %

• 

No setting can be changed when “1 (Lock)” is selected by the lock level 1.

• 

Not displayed when FAIL alarm or control loop break alarm is selected for alarm 1.

Alarm 2 (ALM2)

Set the ALM2 set value. Displayed when any one of the deviation, process and SV alarms is
selected as the alarm 2.
Setting range:

Process alarm, SV alarm: Same as input range
Deviation alarm: 

-span to +span (Within -1999 to +9999 digits)

Factory set value: Temperature input    50 

°

C [

°

F] or 50.0 

°

C [

°

F]

Voltage input  5.0 %

• 

No setting can be changed when “1 (Lock)” is selected by the lock level 1.

• 

Not displayed when FAIL alarm or heater break alarm is selected for alarm 2.

Alarm 3 (ALM3)

Set the ALM3 set value. Displayed when any one of the deviation, process and SV alarms is
selected as the alarm 3.
Setting range: 

Process alarm, SV alarm: Same as input range
Deviation alarm: 

-span to +span (Within -1999 to +9999 digits)

Factory set value: Temperature input    50 

°

C [

°

F] or 50.0 

°

C [

°

F]

Voltage input  5.0 %

• 

No setting can be changed when “1 (Lock)” is selected by the lock level 1.

• 

Not displayed when FAIL alarm is selected for alarm 3.

Proportional band (P)

Set the proportional band for the P control, PI control or PD control.
For heat/cool PID action: Proportional band setting on the heat-side.
Setting range:

0 (0.0) to span (However, 9999 digits or less)

Factory set value: Temperature input    30 

°

C [

°

F] or 30.0 

°

C [

°

F]

Voltage input  3.0 %

• 

No setting can be changed when “1 (Lock)” is selected by the lock level 1.

• 

ON/OFF action when set to 0 (0.0).

Integral time (I)

Set the time of integral action which eliminates the offset occurring in proportional control.
Setting range:

1 to 3600 seconds

OFF (0 second): Integral action OFF (PD action)

Factory set value: 240 seconds

No setting can be changed when “1 (Lock)” is selected by the lock level 1.

(A) 

Continued on the next page.

PV

CH

SV

AREA

PV

CH

SV

AREA

PV

CH

SV

AREA

PV

CH

SV

AREA

PV

CH

SV

AREA

(Option)

(Option)

PV

CH

SV

AREA

PV

CH

SV

AREA

Summary of Contents for MA900 Series

Page 1: ...to avoid electric shock by operating personnel All precautions described in this manual should be taken to avoid damage to the instrument or equipment All wiring must be in accordance with local codes and regulations All wiring must be completed before power is turned on to prevent electric shock instrument failure or incorrect action The power must be turned off before repairing work for input br...

Page 2: ...arm G Deviation high low alarm 4 W SV low alarm H Process high alarm 8 Alarm 2 option 3 N No alarm J Process low alarm A Deviation high alarm K Process high alarm 4 B Deviation low alarm L Process low alarm 4 C Deviation high low alarm M FAIL alarm D Band alarm P Heater break alarm CTL6P 5 6 E Deviation high alarm 4 S Heater break alarm CTL12 5 6 F Deviation low alarm 4 V SV high alarm G Deviation...

Page 3: ...8 1 91 8 Mounting bracket 96 96 Unit mm Rubber option Up to 4 mounting brackets can be used Panel cutout For mounting of the MA900 MA901 panel thickness must be between 1 to 10 mm When mounting multiple MA900 MA901s close together the panel strength should be checked to ensure proper support If the MA900 MA901s have waterproof dustproof options protection will be compromised and not meet IP65 by c...

Page 4: ...size M3 6 Recommended tightening torque 0 4 N m 4 kgf cm 3 2 Terminal Configuration MA900 9 Input 3 4 RTD RTD1 B B A 15 14 13 RTD2 B B A 18 17 16 RTD3 B B A 21 20 19 RTD4 B B A 24 23 22 Thermocouple TC1 15 14 TC2 18 17 TC3 21 20 TC4 24 23 Voltage 15 14 IN1 18 17 IN2 21 20 IN3 24 23 IN4 1 Power Option 6 Contact input RUN STOP Memory area transfer 40 39 DI2 DI1 DI4 42 41 43 DI SET 5 Alarm output Rel...

Page 5: ...8 59 60 1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 1 2 3 5 4 6 7 10 9 With communication or contact input function 5 10 9 8 4 3 RTD and voltage inputs Not isolated between each input channel With heater break alarm function 1 Not isolated between each channel 2 Relationship between CT input and channel number see 7 8 Heater Break Alarm HBA Function P 18 4 PARTS DESCRIPTION This chapter describes various dis...

Page 6: ...channels SET key SET key SET key SET key SET key SET key SET key SET key SET key SET key SET key SET key SET key LbA Lbd AL1 AL2 AL3 P I d Ar Pc db SVrL CH E SV Setting CT Monitor Mode P 7 To PV SV monitor mode SET key Set value SV setting Memory area transfer Current transformer 1 monitor Current transformer 2 monitor SET key SET key SET key SV ArE CT1 CT2 Press the R S key while pressing the SET...

Page 7: ...ge Factory set value Temperature input 0 C F or 0 0 C F Voltage input 0 0 Up to eight memories per channel can be set with one set value SV assumed to be one memory The set values SV corresponding to all of the channels within the same control area can be simultaneously set as the same value No setting can be changed when 1 Lock is selected by the lock level 1 Memory area transfer Selects the memo...

Page 8: ...eferring to monitor value from the current transformer 2 Used only for three phase Displayed only for when the heater break alarm Z 168 is selected as alarm 2 Setting range 0 0 to 100 0 A OFF HBA2 function OFF Factory set value OFF No setting can be changed when 1 Lock is selected by the lock level 1 HBA is not available on a current output Set HBA2 set value to a value about 85 of current transfo...

Page 9: ...an be changed when 1 Lock is selected by the lock level 1 Only the relevant parameter corresponding to the cannel set to MonI or ConT in used unused channels of the parameter setting mode can be scan displayed Lock level 1 Set to the control area now in operation to restrict parameter setting changes by the key operation Setting range 1 Items other than SV and alarms ALM1 to ALM3 0 Unlock 1 Lock 2...

Page 10: ...99 digits Factory set value Temperature input 50 C F or 50 0 C F Voltage input 5 0 No setting can be changed when 1 Lock is selected by the lock level 1 Not displayed when FAIL alarm or control loop break alarm is selected for alarm 1 Alarm 2 ALM2 Set the ALM2 set value Displayed when any one of the deviation process and SV alarms is selected as the alarm 2 Setting range Process alarm SV alarm Sam...

Page 11: ...he lock level 1 In case of MA901 this setting item is not provided Minus setting results in overlap Setting change rate limiter Set the amount of set value SV change per 1 minute when the SV is changed Setting range 0 0 1 to span min OFF Setting change rate limiter OFF Factory set value OFF No setting can be changed when 1 Lock is selected by the lock level 1 The set value SV while the setting cha...

Page 12: ...2 Press the DOWN key three times to change to 1 The display changes to 100 When another area set value SV is changed without changing control area When changing the set value SV corresponding to channel 2 in memory area 3 from 150 C to 100 C with the memory area set to memory area 1 1 Press the SET key in PV SV monitor mode state to transfer to SV setting CT monitor mode 2 Press the R S key to lig...

Page 13: ...ory area transfer The set values SV in other memory areas are simultaneously set to the same value without changing the control area When changing the set values SV corresponding to all of the channels in memory area 2 from 0 C to 300 C with the control area corresponding to memory area 1 1 Press the SET key in PV SV monitor mode state to transfer to SV setting CT monitor mode 2 Press the CH key D...

Page 14: ...n RUN STOP RUN RUN STOP with Key Operation STOP is not displayed dSTP STOP STOP STOP KSTP SToP After the contact is closed it takes a short time until the action of this device is actually selected Therefore pay attention to this delay time if the device is used together with a sequencer etc 0 5 seconds shortest Only SToP is displayed at the time of STOP in the state without RUN STOP transfer by c...

Page 15: ...otuning AT The AT function automatically measures computes and sets the optimum PID and LBA constants If the AT function is activated the optimum PID constants concerning the set value SV in the control area and the LBA setting time can be automatically set Limit cycle system is adopted This function is activated power ON during temperature rise and or when control is stabilized from any process s...

Page 16: ...g items can not be set in MA901 7 4 Setting Change Rate Limiter Function The setting change rate limiter functions so as to change the set value SV gradually toward the set value after being changed This limiter sets how much the set value is changed upward or downward per minute 5 5 Parameter Setting Mode P 10 Example 7 5 Scan Display Function The scan display function is for automatically select...

Page 17: ... alarm set value the alarm relay contact may repeatedly turn on and off due to input fluctuations By the differential gap repeated turning ON and OFF of the relay contact can be prevented Alarm differential gap Temperature input 2 2 0 C F Voltage input 2 0 Low alarm Low High OFF ON Differential gap Low alarm set value SV High alarm Low High OFF ON High alarm set value SV Differential gap Alarm hol...

Page 18: ...ering width within the LBA setting time For reverse action This alarm is produced when the measured value PV does not rise beyond the LBA triggering width within the LBA setting time Control loop break alarm deadband LBD The control loop break alarm may be produced by disturbances other heat sources even if the control system is not abnormal In such a case an area in which no alarm is produced can...

Page 19: ...tric shock always turn off the power before replacing the sensor WARNING Flashing Flashing PV display Input range Effective input range Input range α α The range to be displayed differ depending on the input type or the setting limit α PV flashing display PV display unit Overscale Underscale α PV flashing display 9 REMOVING THE INTERNAL ASSEMBLY Usually this instrument is not necessary to remove t...

Page 20: ...00 times Data storage period Approx 10 years Alarm function Number of points 3 points Option 2 points Alarm type Specify when ordering Deviation high alarm FAIL alarm Deviation low alarm Deviation high alarm with hold action Deviation high low alarm Deviation low alarm with hold action Band alarm Deviation high low alarm with hold action Process high alarm Process high alarm with hold action Proce...

Page 21: ...F N A5 199 9 to 400 0 C 1 2 T 01 T 199 9 to 100 0 C 1 2 T 02 100 0 to 200 0 C T 03 Thermocouple input and RTD input Type Range Code 0 0 to 350 0 C T 04 199 9 to 752 0 F 1 2 T A1 T 100 0 to 200 0 F 2 T A2 100 0 to 400 0 F T A3 0 0 to 450 0 F T A4 0 0 to 752 0 F T A5 W5Re 0 to 2000 C W 01 W26Re 0 to 2320 C W 02 0 to 4000 F W A1 0 to 1300 C A 01 0 to 1390 C A 02 PL II 0 to 1200 C A 03 0 to 2400 F A A...

Page 22: ...nels Memory area No CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8 Set value SV Control loop break alarm Control loop break alarm deadband Alarm 1 Alarm 2 Alarm 3 Proportional band Integral time Derivative time Anti reset windup Cool side proportional band Overlap deadband Setting changing rate limiter Used unused of channels Item Display Set value RKC INSTRUMENT INC HEADQUARTERS 16 6 KUGAHARA 5 CHOME OHTA KU TO...

Reviews: