IMR01H01-E4

7

5.2 PV/SV Monitor Mode

PV/SV monitor mode can confirm the measured value (PV) and the set value (SV). Usually, set to this mode during control execution.
For checking the measured value (PV) and set value (SV) during operation, the following two methods are available.

!"

Checking PV and SV corresponding to each channel

In PV/SV monitor mode, the PV and SV corresponding to the displayed channel can be checked. Each time the CH key is pressed, the

SV corresponding to each channel within the memory area (hereinafter called “control area”) used for control can be checked for each

channel.

Display example:

When the

 

setting change rate limiter is set, a condition in which the set value (SV) goes changing according to that rate of

change is displayed.

If the instrument needs to be switched to RUN or STOP mode, press the <RS key in PV/SV monitor mode. In addition,
RUN/STOP can be selected by key operation or by open or closed contact input (option).

6.3 Transfer of RUN/STOP (P. 14)

!"

Checking SV corresponding to all of the channels within the control area

The SV corresponding to all the channels within the control area are automatically checked at each scan interval time.

5.4 Setup Setting Mode (P. 8), 7.5 Scan Display Function (P. 16)

5.3 SV Setting & CT Monitor Mode

SV setting & CT monitor mode is used to set the set value (SV) and control area or to monitor the current value (current transformer 1,

current transformer 2).

 

Press the SET key with state of PV/SV monitor mode to shift to this mode. The UP, DOWN or <R/S key is used to

change the numeric value, and the SET key is used to change the parameter as well as to register the numeric value.

!"

Description of each parameter

Set value (SV) setting

Set the set value (SV) which is the desired value for control.
Setting range: 

Within input range

Factory set value:  Temperature input    0 

°

C [

°

F] or 0.0 

°

C [

°

F]

Voltage input  0.0 %

• 

Up to eight memories per channel can be set with one set value (SV) assumed to be one

memory.

• 

The set values (SV) corresponding to all of the channels within the same control area can be
simultaneously set as the same value.

• 

No setting can be changed when “1 (Lock)” is selected by the lock level 1.

Memory area transfer

Selects the memory area used for control (Hereafter called the control area).
Setting range: 

1 to 8

Factory set value:  1

• 

No setting can be changed when “1 (Lock)” is selected by the lock level 2.

• 

One set value (SV) and up to eight setting items of the parameter setting mode per channel
can be stored.

For details of the setting items of parameter setting mode, see 

5.5 Parameter Setting

Mode. (P. 10)

Current transformer 1 monitor

Displays the input value of the current transformer 1 used when the instrument is provided with the
heater break alarm 1.
Display range: 

0.0 to 100.0 A

• 

Not displayed when this instrument is not provided with the heater break alarm 1 function.

• 

Displays the input value of the current transformer 1

 

used when the instrument is provided with

the heater break alarm 2 (Z-168).

Current transformer 2 monitor 

[ Correspond to only MA900]

Displays the input value of the current transformer 2 used when the instrument is provided with the
heater break alarm 2 (Z-168).
Display range: 

0.0 to 100.0 A

• 

Not displayed when this instrument is not provided with the heater break alarm 2 function.

• 

In case of MA901, this monitoring screen is not provided.

To PV/SV monitor mode

PV/SV monitor mode display

PV

CH

SV

AREA

PV

CH

SV

AREA

(Option)

(Option)

PV

CH

SV

AREA

PV

CH

SV

AREA

PV

CH

SV

AREA

Indicates that PV corresponding to channel 1
within the control area is 300 

°

C

Indicates that PV corresponding to channel 1
within the control area is 350 

°

C.

Indicates that PV/SV now on display
corresponds to channel 1 within control
area 1.

Indicates that memory area number 1 is
selected as a control area.

Summary of Contents for MA900 Series

Page 1: ...to avoid electric shock by operating personnel All precautions described in this manual should be taken to avoid damage to the instrument or equipment All wiring must be in accordance with local codes and regulations All wiring must be completed before power is turned on to prevent electric shock instrument failure or incorrect action The power must be turned off before repairing work for input br...

Page 2: ...arm G Deviation high low alarm 4 W SV low alarm H Process high alarm 8 Alarm 2 option 3 N No alarm J Process low alarm A Deviation high alarm K Process high alarm 4 B Deviation low alarm L Process low alarm 4 C Deviation high low alarm M FAIL alarm D Band alarm P Heater break alarm CTL6P 5 6 E Deviation high alarm 4 S Heater break alarm CTL12 5 6 F Deviation low alarm 4 V SV high alarm G Deviation...

Page 3: ...8 1 91 8 Mounting bracket 96 96 Unit mm Rubber option Up to 4 mounting brackets can be used Panel cutout For mounting of the MA900 MA901 panel thickness must be between 1 to 10 mm When mounting multiple MA900 MA901s close together the panel strength should be checked to ensure proper support If the MA900 MA901s have waterproof dustproof options protection will be compromised and not meet IP65 by c...

Page 4: ...size M3 6 Recommended tightening torque 0 4 N m 4 kgf cm 3 2 Terminal Configuration MA900 9 Input 3 4 RTD RTD1 B B A 15 14 13 RTD2 B B A 18 17 16 RTD3 B B A 21 20 19 RTD4 B B A 24 23 22 Thermocouple TC1 15 14 TC2 18 17 TC3 21 20 TC4 24 23 Voltage 15 14 IN1 18 17 IN2 21 20 IN3 24 23 IN4 1 Power Option 6 Contact input RUN STOP Memory area transfer 40 39 DI2 DI1 DI4 42 41 43 DI SET 5 Alarm output Rel...

Page 5: ...8 59 60 1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 1 2 3 5 4 6 7 10 9 With communication or contact input function 5 10 9 8 4 3 RTD and voltage inputs Not isolated between each input channel With heater break alarm function 1 Not isolated between each channel 2 Relationship between CT input and channel number see 7 8 Heater Break Alarm HBA Function P 18 4 PARTS DESCRIPTION This chapter describes various dis...

Page 6: ...channels SET key SET key SET key SET key SET key SET key SET key SET key SET key SET key SET key SET key SET key LbA Lbd AL1 AL2 AL3 P I d Ar Pc db SVrL CH E SV Setting CT Monitor Mode P 7 To PV SV monitor mode SET key Set value SV setting Memory area transfer Current transformer 1 monitor Current transformer 2 monitor SET key SET key SET key SV ArE CT1 CT2 Press the R S key while pressing the SET...

Page 7: ...ge Factory set value Temperature input 0 C F or 0 0 C F Voltage input 0 0 Up to eight memories per channel can be set with one set value SV assumed to be one memory The set values SV corresponding to all of the channels within the same control area can be simultaneously set as the same value No setting can be changed when 1 Lock is selected by the lock level 1 Memory area transfer Selects the memo...

Page 8: ...eferring to monitor value from the current transformer 2 Used only for three phase Displayed only for when the heater break alarm Z 168 is selected as alarm 2 Setting range 0 0 to 100 0 A OFF HBA2 function OFF Factory set value OFF No setting can be changed when 1 Lock is selected by the lock level 1 HBA is not available on a current output Set HBA2 set value to a value about 85 of current transfo...

Page 9: ...an be changed when 1 Lock is selected by the lock level 1 Only the relevant parameter corresponding to the cannel set to MonI or ConT in used unused channels of the parameter setting mode can be scan displayed Lock level 1 Set to the control area now in operation to restrict parameter setting changes by the key operation Setting range 1 Items other than SV and alarms ALM1 to ALM3 0 Unlock 1 Lock 2...

Page 10: ...99 digits Factory set value Temperature input 50 C F or 50 0 C F Voltage input 5 0 No setting can be changed when 1 Lock is selected by the lock level 1 Not displayed when FAIL alarm or control loop break alarm is selected for alarm 1 Alarm 2 ALM2 Set the ALM2 set value Displayed when any one of the deviation process and SV alarms is selected as the alarm 2 Setting range Process alarm SV alarm Sam...

Page 11: ...he lock level 1 In case of MA901 this setting item is not provided Minus setting results in overlap Setting change rate limiter Set the amount of set value SV change per 1 minute when the SV is changed Setting range 0 0 1 to span min OFF Setting change rate limiter OFF Factory set value OFF No setting can be changed when 1 Lock is selected by the lock level 1 The set value SV while the setting cha...

Page 12: ...2 Press the DOWN key three times to change to 1 The display changes to 100 When another area set value SV is changed without changing control area When changing the set value SV corresponding to channel 2 in memory area 3 from 150 C to 100 C with the memory area set to memory area 1 1 Press the SET key in PV SV monitor mode state to transfer to SV setting CT monitor mode 2 Press the R S key to lig...

Page 13: ...ory area transfer The set values SV in other memory areas are simultaneously set to the same value without changing the control area When changing the set values SV corresponding to all of the channels in memory area 2 from 0 C to 300 C with the control area corresponding to memory area 1 1 Press the SET key in PV SV monitor mode state to transfer to SV setting CT monitor mode 2 Press the CH key D...

Page 14: ...n RUN STOP RUN RUN STOP with Key Operation STOP is not displayed dSTP STOP STOP STOP KSTP SToP After the contact is closed it takes a short time until the action of this device is actually selected Therefore pay attention to this delay time if the device is used together with a sequencer etc 0 5 seconds shortest Only SToP is displayed at the time of STOP in the state without RUN STOP transfer by c...

Page 15: ...otuning AT The AT function automatically measures computes and sets the optimum PID and LBA constants If the AT function is activated the optimum PID constants concerning the set value SV in the control area and the LBA setting time can be automatically set Limit cycle system is adopted This function is activated power ON during temperature rise and or when control is stabilized from any process s...

Page 16: ...g items can not be set in MA901 7 4 Setting Change Rate Limiter Function The setting change rate limiter functions so as to change the set value SV gradually toward the set value after being changed This limiter sets how much the set value is changed upward or downward per minute 5 5 Parameter Setting Mode P 10 Example 7 5 Scan Display Function The scan display function is for automatically select...

Page 17: ... alarm set value the alarm relay contact may repeatedly turn on and off due to input fluctuations By the differential gap repeated turning ON and OFF of the relay contact can be prevented Alarm differential gap Temperature input 2 2 0 C F Voltage input 2 0 Low alarm Low High OFF ON Differential gap Low alarm set value SV High alarm Low High OFF ON High alarm set value SV Differential gap Alarm hol...

Page 18: ...ering width within the LBA setting time For reverse action This alarm is produced when the measured value PV does not rise beyond the LBA triggering width within the LBA setting time Control loop break alarm deadband LBD The control loop break alarm may be produced by disturbances other heat sources even if the control system is not abnormal In such a case an area in which no alarm is produced can...

Page 19: ...tric shock always turn off the power before replacing the sensor WARNING Flashing Flashing PV display Input range Effective input range Input range α α The range to be displayed differ depending on the input type or the setting limit α PV flashing display PV display unit Overscale Underscale α PV flashing display 9 REMOVING THE INTERNAL ASSEMBLY Usually this instrument is not necessary to remove t...

Page 20: ...00 times Data storage period Approx 10 years Alarm function Number of points 3 points Option 2 points Alarm type Specify when ordering Deviation high alarm FAIL alarm Deviation low alarm Deviation high alarm with hold action Deviation high low alarm Deviation low alarm with hold action Band alarm Deviation high low alarm with hold action Process high alarm Process high alarm with hold action Proce...

Page 21: ...F N A5 199 9 to 400 0 C 1 2 T 01 T 199 9 to 100 0 C 1 2 T 02 100 0 to 200 0 C T 03 Thermocouple input and RTD input Type Range Code 0 0 to 350 0 C T 04 199 9 to 752 0 F 1 2 T A1 T 100 0 to 200 0 F 2 T A2 100 0 to 400 0 F T A3 0 0 to 450 0 F T A4 0 0 to 752 0 F T A5 W5Re 0 to 2000 C W 01 W26Re 0 to 2320 C W 02 0 to 4000 F W A1 0 to 1300 C A 01 0 to 1390 C A 02 PL II 0 to 1200 C A 03 0 to 2400 F A A...

Page 22: ...nels Memory area No CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8 Set value SV Control loop break alarm Control loop break alarm deadband Alarm 1 Alarm 2 Alarm 3 Proportional band Integral time Derivative time Anti reset windup Cool side proportional band Overlap deadband Setting changing rate limiter Used unused of channels Item Display Set value RKC INSTRUMENT INC HEADQUARTERS 16 6 KUGAHARA 5 CHOME OHTA KU TO...

Reviews: