background image

 

   

Digital Controller 

REX-C100/C400/C410/C700/C900 

INSTRUCTION MANUAL 

IMNZC22-E1

 

Thank you for purchasing this RKC product. In order to achieve maximum performance 
and ensure proper operation of your new instrument, carefully read all the instructions 
in this manual. Please place the manual in a convenient location for easy reference. 

 

 

 

 To prevent injury to persons, damage to instrument and equipment, 

a suitable external protection device shall be required. 

 All wiring must be completed before power is turned on to prevent 

electric shock, fire or damage to instrument and equipment. 

 This instrument must be used in accordance with the specifications 

to prevent fire or damage to instrument and equipment. 

 This  instrument  is  not  intended  for  use  in  locations  subject  to 

flammable or explosive gases. 

 Do  not  touch  high-voltage  connections  such  as  power  supply 

terminals, etc. to avoid electric shock. 

 RKC  is  not  responsible  if  this  instrument  is  repaired,  modified  or 

disassembled 

by 

other 

than 

factory-approved 

personnel. 

Malfunction can occur and warranty is void under these conditions. 

 

 

 

This  product  is  intended  for  use  with  industrial  machines,  test  and 
measuring  equipment.  (It  is  not  designed  for  use  with  medical 
equipment and nuclear energy.) 

 

This is a Class A instrument. In a domestic environment, this instrument 
may cause radio interference, in which case the user may be required to 
take additional measures. 

 

This instrument is protected from electric shock by reinforced insulation. 
Provide  reinforced  insulation  between  the  wire  for  the  input  signal  and 
the wires for instrument power supply, source of power and loads. 

 

Be  sure  to  provide  an  appropriate  surge  control  circuit  respectively  for 
the following: 
-  If input/output or signal lines within the building are longer than 30 meters. 
-  If input/output or signal lines leave the building, regardless the length. 

 

This instrument is designed for installation in an enclosed instrumentation 
panel. All high-voltage connections such as power supply terminals must 
be  enclosed  in  the  instrumentation  panel  to  avoid  electric  shock  by 
operating personnel. 

 

All  precautions  described  in  this  manual  should  be  taken  to  avoid 
damage to the instrument or equipment. 

 

All wiring must be in accordance with local codes and regulations. 

 

All  wiring  must  be  completed  before  power  is  turned  on  to  prevent 
electric shock, instrument failure, or incorrect action. The power must be 
turned  off  before  repairing  work  for  input  break  and  output  failure 
including replacement of sensor, contactor or SSR,  and all wiring must 
be completed before power is turned on again. 

 

To prevent instrument damage as a result of failure, protect the power line and 
the input/output lines from high currents with a suitable overcurrent protection 
device with adequate breaking capacity such as fuse, circuit breaker, etc. 

 

Prevent  metal  fragments  or  lead  wire  scraps  from  falling  inside 
instrument case to avoid electric shock, fire or malfunction. 

 

Tighten each terminal screw to the specified torque found in the manual 
to avoid electric shock, fire or malfunction. 

 

For proper operation of this instrument, provide adequate ventilation for 
heat dispensation. 

 

Do  not  connect  wires  to  unused  terminals  as  this  will  interfere  with 
proper operation of the instrument. 

 

Turn off the power supply before cleaning the instrument. 

 

Do  not  use  a  volatile  solvent  such  as  paint  thinner  to  clean  the 
instrument. Deformation or discoloration will occur. Use a soft, dry cloth 
to remove stains from the instrument. 

 

To  avoid  damage  to  instrument  display,  do  not  rub  with  an  abrasive 
material or push front panel with a hard object. 

 

When high alarm with hold action is used for Alarm function, alarm does 
not turn on while hold action is in operation. Take measures to prevent 
overheating which may occur if the control device fails. 

 

NOTICE

 

 

This  manual  assumes that  the  reader has a fundamental knowledge of 
the  principles  of  electricity,  process  control,  computer  technology  and 
communications. 

 

The figures, diagrams and numeric values used in this manual are only 
for purpose of illustration. 

 

RKC  is  not  responsible  for  any  damage  or  injury  that  is  caused  as  a 
result of using this instrument, instrument failure or indirect damage. 

 

RKC is not responsible for any damage and/or injury resulting from the 
use of instruments made by imitating this instrument. 

 

Periodic  maintenance  is  required  for  safe  and  proper  operation  of  this 
instrument.  Some  components  have  a  limited  service  life,  or 
characteristics that change over time. 

 

Every  effort  has  been  made  to  ensure  accuracy  of  all  information 
contained  herein.  RKC  makes  no  warranty  expressed  or  implied,  with 
respect  to  the  accuracy  of  the  information.  The  information  in  this 
manual is subject to change without prior notice. 

 

No  portion  of  this  document  may  be  reprinted,  modified,  copied, 
transmitted,  digitized,  stored,  processed  or  retrieved  through  any 
mechanical,  electronic,  optical  or  other  means  without  prior  written 
approval from RKC. 

1. PRODUCT CHECK

 

 
 
 

(1) Control action

 

F:  PID action with autotuning (Reverse action) 
D:  PID action with autotuning (Direct action) 
W: Heat/Cool PID action with autotuning (Water cooling) 

1

 

A : Heat/Cool PID action with autotuning (Air cooling) 

1

   

(2) Input type

,

 

(3) Range code

 

  Refer to “9. INPUT RANGE TABLE.” 

(4) First control output [OUT1] (Heat-side)

 

M: Relay contact 

G: Trigger for triac driving 

2

 

V:   Voltage pulse 

8:  Current (4 to 20 mA DC) 

(5)

 

Second control output [OUT2] (Cool-side) 

3

 

No symbol: When control action is F or D. 

M: Relay contact 

V:  Voltage pulse 

8:  Current (4 to 20 mA DC) 

(6)

 

Alarm 1 [ALM1],

 

(7) Alarm 2 [ALM2]

 

N:  No alarm 

H:  Process high alarm 

A:  Deviation high alarm 

J:  Process low alarm 

B:  Deviation low alarm 

K:  Process high alarm with hold action 

C:  Deviation high/low alarm 

L:  Process low alarm with hold action 

D:  Band alarm 

P:  Heater break alarm (HBA)[CTL-6] 

4

 

E:  Deviation high alarm 

S:  Heater break alarm (HBA)[CTL-12] 

4

 

 

with hold action 

R:  Control loop break alarm (LBA) 

5

 

F:  Deviation low alarm 

 

 

with hold action 

 

G:  Deviation high/low alarm with hold action 

 

1

 

C100 cannot be specified in Heat/Cool PID action. 

2

 

For  the  C100,  when  control  output  is  trigger  output  for triac  driving,  only  the 
ALM1 is available. 

3

  For the C100, there is no second control output. 

4

 

Heater break alarm (HBA) cannot be specified in case of ALM1. Also, it isn’t 
possible to specify when control output is current output. 

5

 

As control loop break alarm (LBA), only either the ALM1 or ALM2 is selected. 

 

Check that power supply voltage is also the same as that specified 
when ordering. 

 

 

 

 

2. MOUNTING 

 

2.1 Mounting Cautions 

(1) This instrument is intended to be used under the following environmental 

conditions. 

(IEC61010-1)

 

 

[OVERVOLTAGE CATEGORY II, POLLUTION DEGREE 2] 

(2) Use this instrument within the following environment conditions: 

 Allowable ambient temperature: 

0 to 50 

 Allowable ambient humidity:   

45 to 85 % RH 

 Installation environment conditions:  Indoor use, Altitude up to 2000 m 

(3) Avoid the following conditions when selecting the mounting location: 

 Rapid changes in ambient temperature which may cause condensation. 

 Corrosive or inflammable gases. 

 Direct vibration or shock to the mainframe. 

 Water, oil, chemicals, vapor or steam splashes. 

 Excessive dust, salt or iron particles. 

 Excessive induction noise, static electricity, magnetic fields or noise. 

 Direct air flow from an air conditioner. 

 Exposure to direct sunlight. 

 Excessive heat accumulation. 

(4) Mount this instrument in the panel considering the following conditions: 

 Provide adequate ventilation space so that heat does not build up. 

 Do not mount this instrument directly above equipment that generates 

large amount of heat (heaters, transformers, semi-conductor functional 
devices, large-wattage resistors.)

 

 If the ambient temperature rises above 50 

C, cool this instrument with a 

forced  air  fan,  cooler,  etc.  Cooled  air  should  not  blow  directly  on  this 
instrument. 

 In order to improve safety and the immunity to withstand noise, mount 

this  instrument  as  far  away  as  possible  from  high  voltage  equipment, 
power lines, and rotating machinery. 

High voltage equipment:  Do not mount within the same panel. 
Power lines: 

Separate at least 200 mm. 

Rotating machinery: 

Separate as far as possible. 

 For correct functioning mount this instrument in a horizontal position. 

(5) In case this instrument is connected to a supply by means of a permanent 

connection, a switch or circuit-breaker shall be included in the installation. 
This shall be in close proximity to the equipment and within easy reach of 
the  operator.  It  shall  be  marked  as  the  disconnecting  device  for  the 
equipment. 

 

Mounting brackets (C100/400/410/700/900):

  2 

 

Instruction manual (IMNZC22-E1):

   

<Accessories>

CAUTION

 

C100



-

   



(1)(2) (3)

(4)

(6)(7)

C400 
C410 

C700 
C900 



-



   



(1) (2)  (3)  (4)(5)

(6)(7)

*

*

WARNING 

!

 

Summary of Contents for REX-C100

Page 1: ...t responsible for any damage and or injury resulting from the use of instruments made by imitating this instrument Periodic maintenance is required for safe and proper operation of this instrument Some components have a limited service life or characteristics that change over time Every effort has been made to ensure accuracy of all information contained herein RKC makes no warranty expressed or i...

Page 2: ...icinity of the instrument that could affect operation use a noise filter Shorten the distance between the twisted power supply wire pitches to achieve the most effective noise reduction Always install the noise filter on a grounded panel Minimize the wiring distance between the noise filter output and the instrument power supply terminals to achieve the most effective noise reduction Do not connec...

Page 3: ...NC NO OUT 5 6 7 Ground 1 Terminals which are not used according to the controller type are all removed Use the solderless terminal appropriate to the screw size OUT T2 T1 G 5 7 6 Trigger for triac driving OUT 7 6 Voltage pulse Current Relay contact NO OUT2 NO OUT1 4 5 6 7 OUT2 OUT1 4 5 6 7 100 240V AC 24V DC 24V AC 3 3 2 2 3 2 L N L N Voltage pulse Current Input Current transformer input 20 19 CT ...

Page 4: ...ter autotuning is completed AT lamp will go out Control output lamps OUT1 Yellow OUT2 Green OUT1 Lights when control output is turned on OUT2 Lights when cool side control output is turned on 6 DOWN key Decrease numerals 7 UP key Increase numerals To avoid damage to the instrument never use a sharp object to press keys SET This instrument returns to the PV SV display mode if no key operation is pe...

Page 5: ... flow Heater break malfunction of the control device etc When the control output is ON and the current transformer input value is equal to or less than the heater break determination point for the preset number of consecutive sampling cycle an alarm is activated Over current or short circuit When the control output is OFF and the current transformer input value is equal to or greater than the heat...

Page 6: ... key to change 1 to 0 SV PV 6 Press the SET key to store the new set value The display goes to the next parameter and the Initialization mode is unlocked SV PV 7 Press the shift key for 5 seconds while pressing the SET key to go to the Initialization mode When the controller goes to the Initialization mode SL1 will be displayed SV PV SV PV If the control is set to the initial set mode all outputs ...

Page 7: ...ned to ALM2 When the Heater Break Alarm HBA is provided Factory set value varies depending on the instrument specification Set value Details of setting 0000 No alarm 0001 Deviation high alarm 0101 Deviation low alarm 0010 Deviation high low alarm 0110 Band alarm 0011 Process high alarm 0111 Process low alarm 1001 Deviation high alarm with hold action 1101 Deviation low alarm with hold action 1010 ...

Page 8: ...n off the power at once If an error occurs after the power is turned on again please contact RKC sales office or the agent Over scale and Underscale Measured value PV Flashing PV is outside of input range Check Input type Input range and connecting state of sensor Confirm that the sensor or wire is not broken Flashing Over scale PV is above the high input display range limit Flashing Underscale PV...

Reviews: