4. PARTS DESCRIPTION 

 

(1)

 

C100 

PV

 

SV

 

(2)

 

(3)

 

(4)

 

(5)  (6) (7) 

PV

SV

(3)

C410

(1)

(3)

(4)

(5) (6) (7)

PV

 

SV

 

(1)

 

(4)

 

(5)

 

(6)

 

(7)

 

C400 

(2)

 

PV

SV

(1)

 

(3)

(2)

(4)

(5) 

(6) 

(7)

C700, C900 

ALM1

 

ALM2 

OUT 

AT 

REX-

C100

 

SET

 

SET

 

SET

REX-

C400

 

ALM1

ALM2

OUT1 

AT 

OUT2 

(3)

 

REX-

C410

ALM1

ALM2

OUT1

OUT2

AT

REX-

C900

SET

 

(2)

ALM1

 

ALM2 

OUT1 

AT 

OUT2

 

 
 
 
 
 
 
 
 
 
 

5. SETTING 

5.1 Operation Menu 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Input type and input range display 

This instrument immediately confirms the input type symbol and input range following power ON. 
Example: When sensor type of input is K thermocouple. 
 
 
 
 
 
 
 

5.2 Parameter List 

The following parameter symbols are displayed as the SET key is pressed. 

 

Parameter symbols which are not related to existing functions on the controller are not displayed. 

 

Symbol 

Name 

Setting range 

Description 

Factory set value

 

Current 
transformer (CT) 
input value monitor 

0.0 to 100.0 A 
[Display only] 

Display input value from the current transformer. 
[Displayed only when the instrument  has the 
heater break alarm (HBA)] 

 

 

Alarm 1 set value 
(ALM1) 

TC/RTD inputs: 
Deviation alarm, Process alarm: 
 

1999 to +9999  C [ F] or 

 

199.9 to +999.9   C [ F] 

Voltage/Current inputs: 
Deviation alarm: 

199.9 to +200.0 %

Process alarm: 

199.9 to +300.0 %

Set  the  alarm  1  set  value  and  alarm  2  set 
value. 

For the alarm action type, refer to 
page 7. 

Alarm differential gap: 
TC/RTD inputs: 

2 or 2.0  C [ F] 

Voltage/Current inputs:  0.2 % of input span 

TC/RTD inputs: 
50 (50.0) 
 
Voltage/Current 
inputs: 5.0 

 

Alarm 2 set value 
(ALM2) 

 

(4)   

(Set key) 

Used for parameter calling up 
and set value registration. 

 
(5) 

(Shift key) 

Shift digits when settings are 
changed. 

(1) Measured value (PV) display [Green]
Displays PV or various parameter symbols. 

 
(2) Set value (SV) display [Orange] 
Displays SV or various parameter set values (or 
CT input value). 

 
(3) Indication lamps 
Alarm output lamps (ALM1, ALM2) [Red] 
  ALM1: Lights when alarm 1 output is turned on. 
  ALM2: Lights when alarm 2 output is turned on. 

Autotuning (AT) lamp [Green]

Flashes when autotuning is activated. 
(After autotuning is completed: AT lamp 
will go out) 

 

Control output lamps   
(OUT1 [Yellow], OUT2 [Green]) 

OUT1: Lights when control output is 

turned on.* 

OUT2: Lights when cool-side control 

output is turned on. 

(6) 

(DOWN key

Decrease numerals. 

 
(7)   

(UP key

Increase numerals. 

To avoid damage to the instrument,
never use a sharp object to press keys.

 

SET

This instrument returns to the PV/SV 
display mode if no key operation is 
performed for more than one minute.

 

Power ON 

PV/SV Display Mode

 

The controller will display the measured 
value (PV) and the set value (SV).

 

SV Setting Mode

 

SV setting

 

PV 

SV

 

This is the mode used to set the SV.

 

Factory set value: 0 °C [°F] or 0.0 °C [°F]

 

Press the SET key

 

Press

 

and hold 

the SET key 
for 2 seconds.

Input type and Input range Display

 

Automatically 
  (in 4 seconds) 

Press and hold
the SET key 
for 2 seconds.

* Input Type Symbol Table

Symbol 

 

 

 

 

 

 

 

 

Input type

Thermocouple (TC) 

RTD 

Voltage 

input

Current 

input

K J R S B E T N PL II

W5Re/ 

W26Re 

U

 

L

 

JPt 

100 

Pt 

100 

 

Symbol 

PV 

SV 

PV 

SV 

Unit for input and SV display 
(Celsius:  C, Fahrenheit:  F, Voltage/Current inputs: no character shown)

Input type symbol * 

Input range high 

Input range low 

Automatically 

These parameter are not displayed   
in C100 controller.

 

Control loop break 
alarm (LBA) time 

LBA deadband 

Autotuning (AT) 

Proportional 
band 

Integral time 

Derivative time 

Anti-reset 
windup 

Heat-side 
proportioning 

Cool-side 
proportioning 
band

 *

Deadband

 *

Cool-side 
proportioning 
cycle

 *

Set data lock 

Return to the first parameter

SET key 

SET key

SET key

SET key

SET key

SET key

SET key 

SET key 

SET key 

SET key 

SET key

SET key

SET key

Parameters which are not related to existing 
functions on the controller are not displayed. 

(CT) 

(AL1) 

(AL2) 

(HbA) 

(LbA)

(Lbd)

(ATU)

(P) 

(I) 

(D) 

(Ar) 

(T) 

(Pc) 

(db) 

(t) 

(LCK) 

SE T key

 

Current transformer 
(CT) input value 
monitor 

Alarm 1 set value 
(ALM1) 

Alarm 2 set value 
(ALM2) 

Heater break alarm 
(HBA) set value 

SE T key

 

SE T key

 

Parameter Setting Mode 

This mode is used to set the parameters such as alarms, PID constants, etc. (Refer to 5.2 Parameter List.) 
The following parameter symbols are displayed as the SET key is pressed.

P = 0 (0.0): 
ON/OFF action

Summary of Contents for REX-C100

Page 1: ...t responsible for any damage and or injury resulting from the use of instruments made by imitating this instrument Periodic maintenance is required for safe and proper operation of this instrument Some components have a limited service life or characteristics that change over time Every effort has been made to ensure accuracy of all information contained herein RKC makes no warranty expressed or i...

Page 2: ...icinity of the instrument that could affect operation use a noise filter Shorten the distance between the twisted power supply wire pitches to achieve the most effective noise reduction Always install the noise filter on a grounded panel Minimize the wiring distance between the noise filter output and the instrument power supply terminals to achieve the most effective noise reduction Do not connec...

Page 3: ...NC NO OUT 5 6 7 Ground 1 Terminals which are not used according to the controller type are all removed Use the solderless terminal appropriate to the screw size OUT T2 T1 G 5 7 6 Trigger for triac driving OUT 7 6 Voltage pulse Current Relay contact NO OUT2 NO OUT1 4 5 6 7 OUT2 OUT1 4 5 6 7 100 240V AC 24V DC 24V AC 3 3 2 2 3 2 L N L N Voltage pulse Current Input Current transformer input 20 19 CT ...

Page 4: ...ter autotuning is completed AT lamp will go out Control output lamps OUT1 Yellow OUT2 Green OUT1 Lights when control output is turned on OUT2 Lights when cool side control output is turned on 6 DOWN key Decrease numerals 7 UP key Increase numerals To avoid damage to the instrument never use a sharp object to press keys SET This instrument returns to the PV SV display mode if no key operation is pe...

Page 5: ... flow Heater break malfunction of the control device etc When the control output is ON and the current transformer input value is equal to or less than the heater break determination point for the preset number of consecutive sampling cycle an alarm is activated Over current or short circuit When the control output is OFF and the current transformer input value is equal to or greater than the heat...

Page 6: ... key to change 1 to 0 SV PV 6 Press the SET key to store the new set value The display goes to the next parameter and the Initialization mode is unlocked SV PV 7 Press the shift key for 5 seconds while pressing the SET key to go to the Initialization mode When the controller goes to the Initialization mode SL1 will be displayed SV PV SV PV If the control is set to the initial set mode all outputs ...

Page 7: ...ned to ALM2 When the Heater Break Alarm HBA is provided Factory set value varies depending on the instrument specification Set value Details of setting 0000 No alarm 0001 Deviation high alarm 0101 Deviation low alarm 0010 Deviation high low alarm 0110 Band alarm 0011 Process high alarm 0111 Process low alarm 1001 Deviation high alarm with hold action 1101 Deviation low alarm with hold action 1010 ...

Page 8: ...n off the power at once If an error occurs after the power is turned on again please contact RKC sales office or the agent Over scale and Underscale Measured value PV Flashing PV is outside of input range Check Input type Input range and connecting state of sensor Confirm that the sensor or wire is not broken Flashing Over scale PV is above the high input display range limit Flashing Underscale PV...