background image

 

5.3 Changing Parameter Settings 

Procedures to change parameter settings are shown below. 
 
 
 
 
 
 
 

 Change the set value (SV) 

Change the set value (SV) from 0  C to 200  C 
1. Select the SV setting mode 
Press the SET key at PV/SV monitor screen until SV setting screen is displayed. 

 

SV 

PV 

SV

PV

 

2. Shift the high-lighted digit 
Press the shift key to high-light the hundreds digit. 
The high-lighted digit indicates which digit can be set. 

 

SV 

PV 

SV

PV

 

3. Change the set value 
Press the UP key to change the number to 2. 

 

SV 

PV 

SV

PV

 

4. Store the set value 
Press  the  SET  key  to  store  the  new  set  value.  The  display  returns  to  the 
PV/SV monitor screen. 

 

SV 

PV 

SV

PV

 

 Change parameters other than the set value (SV) 

The  changing  procedures  are  the  same  as  those  of  example  2  to  4  in  the 
above "

 Change the set value (SV)". Pressing the SET key after the setting 

end shifts to the next parameter. When no parameter setting is required, return 
the instrument to the PV/SV display mode. 
 

6. OPERATION 

 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

6.1 Operating Precautions 

(1)  All mounting and wiring must be completed before the power is turned on. 
(2)  The  settings  for  the  SV  and  all  parameters  should  be appropriate  for  the 

controlled object. 

(3)  A  power  supply  switch  is  not  furnished  with  this  instrument.  It  is  ready  to 

operate as soon as the power is turned on. 
 

6.2 Set Data Lock (LCK) Function 

The  set  data  lock  restricts  parameter  setting  changes  by  key  operation.  This 
function prevents the operator from making errors during operation. 

 

Set value 

Parameters which can be changed 

0100 

All parameters [Factory set value] 

0101 

No parameters [All Locked] 

0110 

SV 

 

Parameters protected by Set Data Lock function are still displayed  for 
monitoring.

 

 

6.3 Autotuning (AT) Function 

Autotuning (AT) automatically measures, calculates and sets the optimum PID 
and  LBA  constants.  The  following  conditions  are  necessary  to  carry  out 
autotuning and the conditions which will cause the autotuning to stop.

 

 

Caution for using the Autotuning (AT) 
When  a  temperature  change  (UP  and/or  Down)  is  1  C  or  less  per 
minute  during  Autotuning,  Autotuning  may  be  cancelled  before 
calculating PID values. In that case, adjust the PID values manually. It 
is  possible  to  happen  when  the  set  value  is  around  the  ambient 
temperature or is close to the maximum temperature achieved by the 
load. 

  Requirements for AT start 

Start the autotuning when all following conditions are satisfied: 

  Prior to starting the AT function, end all the parameter settings other than PID and LBA. 
  Confirm the LCK function has not been engaged. 

 

When  the  autotuning  is  finished,  the  controller  will  automatically  returns  to 
PID control. 

 

  Requirements for AT cancellation 

The autotuning is canceled if any of the following conditions exist. 

  When the set value (SV) is changed. 
  When the PV bias value is changed. 
  When the PV becomes abnormal due to burnout. 
  When the power is turned off. 
  When power failure longer than 20 ms occurs. 

 

If the AT is canceled, the controller immediately changes to PID control. The 

PID values will be the same as before AT was activated. 

 

When AT is completed, the controller immediately changes to PID control. If 
the  control  system  does  not  allow  the  AT  cycling  process,  set  each  PID 
constant manually to meet the needs of the application. 

 

7. INITIAL SETTING 

 
 
 
 
 
 
 
 

 

7.1

 

Go to Initialization Mode

 

1. 

Turn  on  the  power  to  this  controller.  The  instrument  goes  to  the PV/SV 
display after confirming input type symbol and input range. 

2. 

Press and hold the SET key for 5 seconds to go to the Parameter setting 
mode from the PV/SV display. 

3. 

Press the SET key until “LCK” (Set Data Lock display) will be displayed. 

4. 

The  high-lighted digit indicates  which digit can be set. Press shift key to 
high-light  the  hundreds  digit.  (The        section  in  each  image  of  the 
controller shows the digits which are not high-lighted.) 

 

SV

PV

 

5. 

Press the DOWN key to change 1 to 0. 

 

SV

PV

 

6. 

Press  the  SET  key  to  store  the  new  set  value.  The  display  goes  to  the 
next parameter, and the Initialization mode is unlocked. 

 

SV

PV

 

7. 

Press the shift key for 5 seconds while pressing the SET key to go to the 
Initialization  mode.  When  the  controller  goes  to  the  Initialization  mode, 
“SL1” will be displayed. 

 

SV 

PV 

SV

PV

 

If the control is set to the initial set mode, all outputs are turned OFF. 

 

7.2

 

Exit Initialization Mode

 

When  any  parameter  setting  is  changed  in  the  Initialization  mode, 
check  all  parameter  set  values  in  SV  setting  mode  and  Parameter 
setting mode. 

1. 

Press  the  shift  key  for  5  seconds  while  pressing  the  SET  key  from  any 
display in the Initialization mode. The controller goes back to the operation 
mode and the PV/SV display will be displayed. 

2. 

Press and hold the SET key for 5 seconds in the PV/SV display. 

3. 

Press the SET key until “LCK” (Set Data Lock display) will be displayed. 

4. 

The  high-lighted  digit indicates  which  digit can  be  set.  Press  shift  key  to 
high-light the hundreds digit. 

 

SV

PV

 

5. 

Press  the  SET  key  to  store  the  new  set  value.  The  display  goes  to  the 
next parameter, and the Initialization mode is locked. 

 

 

 

To store a new value for the parameter, always press the SET key. 
The display changes to the next parameter and the new value will be stored.

  A  new  value  will  not  be  stored  without  pressing  SET  key  after  the  new 

value is displayed on the display. 

  After a new value has been displayed by using the UP and DOWN keys, 

the  SET  key  must  be  pressed  within  1  minute,  or  the  new  value  is  not 
stored and the display will return to the PV/SV monitor screen. 

PV/SV monitor display 

(PV/SV display mode) 

SV setting display
(SV setting mode) 

PV/SV monitor display
(PV/SV display mode)

 

Parameters in  the  Initialization mode should be set according  to  the 
application  before  setting  any  parameter  related  to  operation.  Once 
the Parameters in the Initialization mode are set correctly, no further 
changes  need  to  be  made  to  parameters  for  the  same  application 
under  normal  conditions.  If  they  are  changed  unnecessarily,  it  may 
result  in  malfunction  or  failure  of  the  instrument.  RKC  will  not  bear 
any  responsibility  for  malfunction  or  failure  as  a  result  of  improper 
changes in the Initialization mode. 

Set data lock function display

Set value 
0: Initialization mode unlocked
1: Initialization mode locked 

CT1 input value display

 
The parameter displayed varies   
on the instrument specification.

 

Initialize code 
selection display 
of initialization 
mode 

CT1 input  value
display

CAUTIONS

 

  All mounting and wiring must be completed before the power is turned 

on.  If  the  input  signal wiring  is  disconnected  or short-circuited  (RTD 
input only), the instrument determines that burnout has occurred. 

  Displays: 

 Upscale: 

Thermocouple input, RTD input (when input break) 

 Downscale:  Thermocouple input (specify when ordering), 

 

RTD input (when short-circuited), 

 

Voltage input (1 to 5 V DC), Current input (4 to 20 mA DC)

 For the voltage (0 to 5 V DC) or current (0 to 20 mA DC) input, the 

display becomes indefinite (display of about zero value). 

  Outputs: 

 Control output:  OFF (Heat/Cool control: the control output on 

 

 

both heat-side and cool-side is turned off) 

 Alarm output:  Both  of  the  Alarm  1  and  Alarm  2  outputs  of  this 

instrument  are  turned  on  when  burnout  occurs 
regardless  of  any  of  the  following actions taken.  (High 
alarm,  low  alarm,  etc.)  In  addition,  when  used  for  any 
purposes other than these alarms (event, etc.), specify 
the Z-124 specification (not to be forcibly turned on).

 

  A power failure of 20 ms or  less will not affect the control action. 

When  a  power  failure  of  more  than  20  ms  occurs,  the  instrument 
assumes that the power has been turned off. When power returns, 
the controller will retain the conditions that existed prior to shut down.

  The  alarm  hold  action  is  activated  when  not  only  the  power  is 

turned on, but also the SV is changed. 

Set data lock function display

CT1 input value display 

 
The parameter displayed varies on 
the instrument specification. 

 

SV

PV

WARNING 

!

 

Summary of Contents for REX-C100

Page 1: ...t responsible for any damage and or injury resulting from the use of instruments made by imitating this instrument Periodic maintenance is required for safe and proper operation of this instrument Some components have a limited service life or characteristics that change over time Every effort has been made to ensure accuracy of all information contained herein RKC makes no warranty expressed or i...

Page 2: ...icinity of the instrument that could affect operation use a noise filter Shorten the distance between the twisted power supply wire pitches to achieve the most effective noise reduction Always install the noise filter on a grounded panel Minimize the wiring distance between the noise filter output and the instrument power supply terminals to achieve the most effective noise reduction Do not connec...

Page 3: ...NC NO OUT 5 6 7 Ground 1 Terminals which are not used according to the controller type are all removed Use the solderless terminal appropriate to the screw size OUT T2 T1 G 5 7 6 Trigger for triac driving OUT 7 6 Voltage pulse Current Relay contact NO OUT2 NO OUT1 4 5 6 7 OUT2 OUT1 4 5 6 7 100 240V AC 24V DC 24V AC 3 3 2 2 3 2 L N L N Voltage pulse Current Input Current transformer input 20 19 CT ...

Page 4: ...ter autotuning is completed AT lamp will go out Control output lamps OUT1 Yellow OUT2 Green OUT1 Lights when control output is turned on OUT2 Lights when cool side control output is turned on 6 DOWN key Decrease numerals 7 UP key Increase numerals To avoid damage to the instrument never use a sharp object to press keys SET This instrument returns to the PV SV display mode if no key operation is pe...

Page 5: ... flow Heater break malfunction of the control device etc When the control output is ON and the current transformer input value is equal to or less than the heater break determination point for the preset number of consecutive sampling cycle an alarm is activated Over current or short circuit When the control output is OFF and the current transformer input value is equal to or greater than the heat...

Page 6: ... key to change 1 to 0 SV PV 6 Press the SET key to store the new set value The display goes to the next parameter and the Initialization mode is unlocked SV PV 7 Press the shift key for 5 seconds while pressing the SET key to go to the Initialization mode When the controller goes to the Initialization mode SL1 will be displayed SV PV SV PV If the control is set to the initial set mode all outputs ...

Page 7: ...ned to ALM2 When the Heater Break Alarm HBA is provided Factory set value varies depending on the instrument specification Set value Details of setting 0000 No alarm 0001 Deviation high alarm 0101 Deviation low alarm 0010 Deviation high low alarm 0110 Band alarm 0011 Process high alarm 0111 Process low alarm 1001 Deviation high alarm with hold action 1101 Deviation low alarm with hold action 1010 ...

Page 8: ...n off the power at once If an error occurs after the power is turned on again please contact RKC sales office or the agent Over scale and Underscale Measured value PV Flashing PV is outside of input range Check Input type Input range and connecting state of sensor Confirm that the sensor or wire is not broken Flashing Over scale PV is above the high input display range limit Flashing Underscale PV...

Reviews: