7
7.3 Initial Setting Menu
Display flowcharts in Initialization mode are shown in the following.
Do not change to the section parameters and any parameter in
the Initialization mode which is not described in the initial setting
menu below. It may result in malfunction or failure of the instrument.
7.4 Input Type Selection (SL1)
When any parameter setting is changed in the Initialization mode,
check all parameter set values in SV setting mode and Parameter
setting mode.
Factory set value varies depending on the input type.
Set value
Input type
Hardware
0000
K
Thermocouple
(TC)
A
0001
J
0010
L
0011
E
0100
N
0111
R
1000
S
1001
B
1010
W5Re/W26Re
1011
PL II
0101
T
B
0110
U
1100
Pt100 (JIS/IEC)
RTD
C
1101
JPt100 (JIS)
1110
0 to 5 V DC
Voltage
D
1111
1 to 5 V DC
1110
0 to 20 mA DC
Current
E
1111
4 to 20 mA DC
Conduct setting so as to meet the instrument specification (input type).
Setting change between different symbols may cause malfunction,
but the setting can be changed when hardware types have the same
symbol. However, when the setting is changed, always reset “SLH”
and “SLL” (Refer to page 8).
Change Settings
Example: Change the input type from “K” to “J”
1. Press the SET key. The display will go to SL1.
2. Press the UP key to change the number to 1.
3. Press the SET key to store the new set value.
The display goes to the next parameter.
7.5 Temperature Unit and Cooling Type
Selection (SL2)
Inappropriate settings may result in malfunction. Control type between
Heat Only and Heat/Cool cannot be changed by this parameter.
Factory set value varies depending on the instrument specification.
Set
value
Description
Temperature
unit
Cooling type selection
0000
C
Air cooling (A type) or Heat only type (F, D type)
0001
F
Air cooling (A type) or Heat only type (F, D type)
0010
C
Water cooling (W type)
0011
F
Water cooling (W type)
Change Settings
Example: Change the temperature unit of the Heat only type
from “ C (0000)” to “ F (0001)”
1.
Press the SET key until SL2 is displayed.
2.
Press the UP key to change the number to 1.
SV
PV
SV
PV
3.
Press the SET key to store the new set value. The display goes to the
next parameter.
7.6 Alarm 1 [ALM1] Type Selection (SL4)
Alarm 2 [ALM2] Type Selection (SL5)
If the alarm function is not provided with the instrument when shipped from the
factory, no alarm output is available by changing SL4 and/or SL5.
SL4 is set to 0000 in the following cases.
When the instrument does not have ALM1 output
When Control Loop Break Alarm (LBA) is provided and assigned
to ALM1
SL5 is set to 0000 in the following cases.
When the instrument does not have ALM2 output
When Control Loop Break Alarm (LBA) is provided and assigned
to ALM2
When the SV alarm is provided and assigned to ALM2
When the Heater Break Alarm (HBA) is provided
Factory set value varies depending on the instrument specification.
Set value
Details of setting
0000
No alarm
0001
Deviation high alarm
0101
Deviation low alarm
0010
Deviation high/low alarm
0110
Band alarm
0011
Process high alarm
0111
Process low alarm
1001
Deviation high alarm with hold action *
1101
Deviation low alarm with hold action *
1010
Deviation high/low alarm with hold action *
1011
Process high alarm with hold action *
1111
Process low alarm with hold action *
* Hold action:
When Hold action is ON, the alarm action is suppressed at start-up or the
control set value change until the measured value enters the non-alarm range.
Alarm action type
Both of the Alarm 1 and Alarm 2 outputs of this instrument are turned on when
burnout occurs regardless of any of the following actions taken (High alarm, low
alarm, etc.). In addition, when used for any purposes other than these alarms
(event, etc.), specify the Z-124 specification (not to be forcibly turned on).
( : SV : Alarm set value
☆
: Alarm differential gap)
Deviation high alarm
Deviation high/low alarm
Deviation low alarm
(Alarm set value is less than 0.)
(Alarm set value is less than 0.)
Low
High
OFF
ON
PV
OFF
ON
PV
Low
High
OFF
ON
PV
Low
High
OFF
ON
PV
Low
High
OFF
ON
PV
Low
High
(Alarm set value is greater than 0.)
(Alarm set value is greater than 0.)
ON
OFF
PV
Band alarm
Process low alarm
Process high alarm
OFF
OFF
ON
PV
Low
High
Low
High
OFF
ON
PV
Low
High
ON
☆
☆
☆
☆
☆
☆
☆
☆
☆
☆
Change Settings
Example: Change the ALM1 type from “Deviation high alarm (0001)” to
“Deviation low alarm (0101)”
1.
Press the SET key three times at SL1 until SL4 is displayed.
2.
Press the shift key to high-light the hundreds digit.
3.
Press the UP key to change the number to 1.
4.
Press the SET key to store the new set value. The display goes to the
next parameter.
7.7 PV bias (Pb)
The value set in the PV bias is added to the input value (actual measured
value) to correct the input value. The PV bias is used to correct the individual
variations in the sensors or when there is difference between the measured
values (PV) of other instruments.
Setting range:
TC/RTD inputs:
1999 to +9999 C [ F] or
199.9 to +999.9 C [ F]
Voltage/Current inputs:
199.9 to +200.0 %
Factory set value:
TC/RTD inputs:
0 C [ F] or 0.0 C [ F]
Voltage/Current inputs: 0.0 %
Continued on the next page.
Input type selection
SV
PV
SV
PV
Press the shift key while pressing
the SET key for 5 seconds with
the unlocked.
PV/SV display mode or Parameter setting mode
Input type selection
SET key
(SL1)
SET key
SET key
Alarm1 type
selection
SET key
(SL4)
Alarm2 type
selection
SET key
(SL5)
SET key
SET key
SET key
PV bias
SET key
(Pb)
ON/OFF action
differential gap
SET key
(oH)
Alarm 1 differential gap
SET key
(AH1)
Alarm 2 differential gap
SET key
(AH2)
Setting limiter high
SET key
(SLH)
Setting limiter low
SET key
(SLL)
Temperature unit and
cooling type selection
SV
PV
SV
PV