Continued from the previous page.
Change Settings
Example: When the temperature is measured by two instruments
When the measured values (PV) are as shown in the following:
Main unit = 198 C
Recorder = 200 C
If a PV bias correction value of +2 C is added to the measured value the
main unit, the displayed value become:
Displayed value = Measured value (PV) + PV bias
= 198 C + 2 C = 200 C
The setting procedures is described in the following.
1. Press the SET key at “Pb” is displayed.
2. Press the UP key to change the number to 2.
3.
Press the SET key to store the new set value.
The display goes to the next parameter.
7.8 ON/OFF Action Differential Gap (oH)
Setting range:
TC/RTD inputs:
0 to 100 C [ F] or
0.0 to 100.0 C [ F]
Voltage/Current inputs:
199.9 to
200.0 %
Factory set value: TC/RTD inputs:
2 C [ F] or 2.0 C [ F]
Voltage/Current inputs: 0.2 % of input span
Change Settings
Example: Change the On/Off Action differential gap from “2 C” to “4 C”
1. Press the SET key at “oH” is displayed.
2. Press the UP key to change the number to 4.
3. Press the SET key to store the new set value. The display goes to the
next parameter.
7.9 Alarm 1 Differential Gap (AH1)
Alarm 2 Differential Gap (AH2)
Setting range:
TC/RTD inputs:
0 to 100 C [ F] or
0.0 to 100.0 C [ F]
Voltage/Current inputs: 0.0 to 10.0 %
Factory set value: TC/RTD inputs:
2 C [ F] or 2.0 C [ F]
Voltage/Current inputs: 0.2 % of input span
Change Settings
Example: Change the Alarm 1 differential gap from “2 C” to “4 C”
1. Press the SET key at “AH1” is displayed.
2. Press the UP key to change the number to 4.
3. Press the SET key to store the new set value. The display goes to the
next parameter.
7.10 Setting Limiter High (SLH)
Setting Limiter Low (SLL)
For voltage or current input, set scaling within the input range.
Refer to 9. INPUT RANGE TABLE.
Factory set value varies depending on the instrument specification.
Input type
Setting range *
K
0 to 1372 C
0 to 2502 F
J
0 to 1200 C
0 to 2192 F
R
0 to 1769 C
0 to 3216 F
S
0 to 1769 C
0 to 3216 F
B
0 to 1820 C
0 to 3308 F
TC
E
0 to 1000 C
0 to 1832 F
N
0 to 1300 C
0 to 2372 F
T
199.9 to
400.0 C
199.9 to
752.0 F
W5Re/W26Re
0 to 2320 C
0 to 4208 F
PLII
0 to 1390 C
0 to 2534 F
U
199.9 to
600.0 C
199.9 to
999.9 F
L
0 to 800 C
0 to 1600 F
RTD
Pt100
199.9 to
649.0 C
199.9 to 999.9 F
JPt100
199.9 to
649.0 C
* Limit setting becomes SLH SLL.
When changing the high-limit (SLH) and the low-limit (SLL) limiter
settings, always set the set-value (SV) within the limiter range.
Change Settings
Example: The input range (input scale range) is from 0.0 to 100.0 C,
the setting limiter high is 80.0 C.
1.
Press the SET key at “SLH” is displayed.
2.
Press the shift key to high-light the tens digit.
3.
Press the DOWN key to change the number to 8.
4.
Press the SET key to store the new set value.
The display goes to the next parameter.
8. ERROR DISPLAYS
Error display
RAM failure (Incorrect
set data write, etc.)
Turn off the power at once. If an
error occurs after the power is
turned on again, please contact
RKC sales office or the agent.
Over-scale and Underscale
Measured value (PV)
[Flashing]
PV is outside of input
range.
Check Input type, Input range
and
connecting
state
of
sensor.
Confirm
that
the
sensor or wire is not broken.
[Flashing]
Over-scale:
PV is above the high
input display range limit.
[Flashing]
Underscale:
PV is below the low
input display range limit.
9. INPUT RANGE TABLE
TC/RTD inputs
Input type
Range
Code
Range
Code
Range
Code
0 to 200 C
K 01
0 to 400 C
K 02
0 to 600 C
K 03
0 to 800 C
K 04
0 to 1000 C
K 05
0 to 1200 C
K 06
K
0 to 1372 C
K 07
0 to 100 C
K 13
0 to 300 C
K 14
0 to 450 C
K 17
0 to 500 C
K 20
0 to 800 F
K A1
0 to 1600 F
K A2
0 to 2502 F
K A3
20 to 70 F
K A9
0 to 200 C
J
01
0 to 400 C
J 02
0 to 600 C
J
03
J
0 to 800 C
J
04
0 to 1000 C
J 05
0 to 1200 C
J
06
0 to 450 C
J
10
0 to 800 F
J A1
0 to 1600 F
J A2
0 to 2192 F
J A3
0 to 400 F
J A6
0 to 300 F
J A7
R
1
0 to 1600 C
R 01
0 to 1769 C
R 02
0 to 1350 C
R 04
0 to 3200 F
R A1
0 to 3216 F
R A2
S
1
0 to 1600 C
S 01
0 to 1769 C
S 02
0 to 3200 F
S A1
0 to 3216 F
S A2
B
2
400 to 1800 C
B 01
0 to 1820 C
B 02
800 to 3200 F
B A1
TC
0 to 3308 F
B A2
E
0 to 800 C
E 01
0 to 1000 C
E 02
0 to 1600 F
E A1
0 to 1832 F
E A2
N
0 to 1200 C
N 01
0 to 1300 C
N 02
0 to 2300 F
N A1
0 to 2372 F
N A2
199.9 to
400.0 C
T 01
199.9 to
100.0 C T 02
100.0 to
200.0 C
T 03
T
0.0 to 350.0 C
T 04
199.9 to
752.0 F T A1
100.0 to
200.0 F
T A2
100.0 to
400.0 F
T A3
0.0 to 450.0 F
T A4
0.0 to 752.0 F
T A5
W5Re/W26Re
0 to 2000 C
W 01
0 to 2320 C
W 02
0 to 4000 F
W A1
PLII
0 to 1300 C
A 01
0 to 1390 C
A 02
0 to 1200 C
A 03
0 to 2400 F
A A1
0 to 2534 F
A A2
U
199.9 to
600.0 C
U 01
199.9 to
100.0 C U 02
0.0 to 400.0 C
U 03
199.9 to
999.9 F
U A1
100.0 to
200.0 F U A2
0.0 to 999.9 F
U A3
L
0 to 400 C
L 01
0 to 800 C
L 02
0 to 800 F
L A1
0 to 1600 F
L A2
199.9 to
649.0 C
D 01
199.9 to
200.0 C D 02
100.0 to
50.0 C
D 03
100.0 to
100.0 C
D 04
100.0 to
200.0 C D 05
0.0 to 50.0 C
D 06
0.0 to 100.0 C
D 07
0.0 to 200.0 C
D 08
0.0 to 300.0 C
D 09
Pt100
0.0 to 500.0 C
D 10
199.9 to
999.9 F D A1
199.9 to
400.0 F
D A2
199.9 to
200.0 F
D A3
100.0 to
100.0 F D A4
100.0 to
300.0 F
D A5
RTD
0.0 to 100.0 F
D A6
0.0 to 200.0 F
D A7
0.0 to 400.0 F
D A8
0.0 to 500.0 F
D A9
199.9 to
649.0 C
P 01
199.9 to
200.0 C P 02
100.0 to
50.0 C
P 03
JPt100
100.0 to
100.0 C
P 04
100.0 to
200.0 C P 05
0.0 to 50.0 C
P 06
0.0 to 100.0 C
P 07
0.0 to 200.0 C
P 08
0.0 to 300.0 C
P 09
0.0 to 500.0 C
P 10
1
0 to 399 °C [0 to 799 °F]: 6 °C [12 °F]
2
0 to 399 °C [0 to 799 °F]: Accuracy is not guaranteed.
Voltage/Current inputs
Type
Range
Code
Type
Range
Code
0 to 5 V DC
0.0 to 100.0 (Fixed)
4
01
0 to 20 mA DC
0.0 to 100.0 (Fixed)
7
01
1 to 5 V DC
0.0 to 100.0 (Fixed)
6
01
4 to 20 mA DC
0.0 to 100.0 (Fixed)
8
01
SV
PV
Setting limiter [high] display
SV
PV
SV
PV
SV
PV
SV
PV
0.0 C
100.0 C
80.0 C
Setting limiter
high
To prevent electric shock,
always turn off the power
before replacing the sensor.
WARNING
!