Module Type Controller 

SRV

 

Temperature Control Module for PROFIBUS 

V-TIO-G/V-TIO-H

 

Instruction Manual

 

IMS01P06-E2

 

 
Thank you for purchasing this RKC product. In order to 
achieve maximum performance and ensure proper operation 
of your new instrument, carefully read all the instructions in 
this manual. Please place this manual in a convenient 
location for easy reference. 
 

 

SYMBOLS 

:  This mark indicates precautions that must be 

taken if there is danger of electric shock, fire, 
etc., which could result in loss of life or injury. 

 

:  This mark indicates that if these precautions 

and operating procedures are not taken, 
damage to the instrument may result. 

 

:  This mark indicates that all precautions should 

be taken for safe usage. 

 

:  This mark indicates important information on 

installation, handling and operating 
procedures. 

 

:  This mark indicates supplemental information 

on installation, handling and operating 
procedures. 

 

This mark indicates where additional 
information may be located. 

 
 
 
 

 

An external protection device must be installed if 
failure of this instrument could result in damage to 
the instrument, equipment or injury to personnel. 

 

All wiring must be completed before power is turned 
on to prevent electric shock, fire or damage to 
instrument and equipment. 

 

This instrument must be used in accordance with the 
specifications to prevent fire or damage to 
instrument and equipment.   

 

This instrument is not intended for use in locations 
subject to flammable or explosive gases. 

 

Do not touch high-voltage connections such as 
power supply terminals, etc. to avoid electric shock. 

 

RKC is not responsible if this instrument is repaired, 
modified or disassembled by other than 
factory-approved personnel. Malfunction can occur 
and warranty is void under these conditions. 

 
 
 
 

 

 

This is a Class A instrument. In a domestic environment, 
this instrument may cause radio interference, in which 
case the user may be required to take adequate measures. 

 

 

 

This instrument is protected from electric shock by 
reinforced insulation. Provide reinforced insulation between 
the wire for the input signal and the wires for instrument 
power supply, source of power and loads. 

 

Be sure to provide an appropriate surge control circuit 
respectively for the following: 

 If input/output or signal lines within the building are 

longer than 30 meters. 

 If input/output or signal lines leave the building, 

regardless the length. 

 

This instrument is designed for installation in an enclosed 
instrumentation panel. All high-voltage connections such 
as power supply terminals must be enclosed in the 
instrumentation panel to avoid electric shock by operating 
personnel. 

 

All precautions described in this manual should be taken to 
avoid damage to the instrument or equipment. 

 

All wiring must be in accordance with local codes and 
regulations.  

 

All wiring must be completed before power is turned on to 
prevent electric shock, instrument failure, or incorrect 
action. 
The power must be turned off before repairing work for 
input break and output failure including replacement of 
sensor, contactor or SSR, and all wiring must be 
completed before power is turned on again. 

 

To prevent instrument damage or failure, protect the power 
line and the input/output lines from high currents with a 
protection device such as fuse, circuit breaker, etc. 

 

Prevent metal fragments or lead wire scraps from falling 
inside instrument case to avoid electric shock, fire or 
malfunction. 

 

Tighten each terminal screw to the specified torque found 
in the manual to avoid electric shock, fire or malfunction. 

 

For proper operation of this instrument, provide adequate 
ventilation for heat dispensation. 

 

Do not connect wires to unused terminals as this will 
interfere with proper operation of the instrument. 

 

Turn off the power supply before cleaning the instrument. 

 

Do not use a volatile solvent such as paint thinner to clean 
the instrument. Deformation or discoloration will occur. Use 
a soft, dry cloth to remove stains from the instrument. 

 

To avoid damage to instrument display, do not rub with an 
abrasive material or push front panel with a hard object. 

 

Do not connect modular connectors to telephone line. 

 

NOTICE 

 

This manual assumes that the reader has a fundamental 
knowledge of the principles of electricity, process control, 
computer technology and communications. 

 

The figures, diagrams and numeric values used in this 
manual are only for purpose of illustration.   

 

RKC is not responsible for any damage or injury that is 
caused as a result of using this instrument, instrument 
failure or indirect damage. 

 

RKC is not responsible for any damage and/or injury 
resulting from the use of instruments made by imitating this 
instrument. 

 

Periodic maintenance is required for safe and proper 
operation of this instrument. Some components have a 
limited service life, or characteristics that change over time. 

 

Every effort has been made to ensure accuracy of all 
information contained herein. RKC makes no warranty 
expressed or implied, with respect to the accuracy of the 
information. The information in this manual is subject to 
change without prior notice. 

 

No portion of this document may be reprinted, modified, 
copied, transmitted, digitized, stored, processed or 
retrieved through any mechanical, electronic, optical or 
other means without prior written approval from RKC. 

 

 

WARNING

 

CAUTION

 

!

 

!

 

WARNING 

CAUTION

 

Summary of Contents for V-TIO-G

Page 1: ...nals must be enclosed in the instrumentation panel to avoid electric shock by operating personnel All precautions described in this manual should be taken to avoid damage to the instrument or equipment All wiring must be in accordance with local codes and regulations All wiring must be completed before power is turned on to prevent electric shock instrument failure or incorrect action The power mu...

Page 2: ...mon code Thermocouple input Type Code Range Code Range K K02 0 to 400 C KB9 32 to 752 F K04 0 to 800 C KB8 32 to 1472 F K16 200 to 1372 C KB7 328 to 2501 F K09 0 0 to 400 0 C KC2 32 0 to 752 0 F K35 200 0 to 400 0 C KC1 328 0 to 752 0 F J J02 0 to 400 C JC2 32 to 752 F J04 0 to 800 C JC1 32 to 1472 F J15 200 to 1200 C JB9 328 to 2192 F J09 0 0 to 400 0 C JC4 32 0 to 752 0 F J27 200 0 to 400 0 C JC...

Page 3: ... A green lamp turns on RX TX for PROFIBUS communication During data send and receive A green lamp turns on 4 COMMUNICATION SETTING Set communication setting before mounting and wiring of SRV Do not separate the module mainframe from the terminal base with the power turned on If separated adjusted data may be destroyed control be stopped and no return can be made 4 1 Address Setting PROFIBUS addres...

Page 4: ...protocol Modbus Factory set value of the dip switch 1 No 1 OFF No 5 OFF No 2 OFF No 6 OFF No 3 OFF No 7 OFF No 4 OFF No 8 OFF For host communication Modbus see the Module Type Controller SRV Communication Instruction Manual IMS01P01 E 4 3 Host Communication Setting With the dip switch 2 which there is on the right side of module select communication speed for host communication When host communica...

Page 5: ... connector but the same also when not provided with the connector Depth in connector mounting Conduct installation in consideration of the sizes of the connector and cable when connector connected Unit mm Provide space in consideration of the sizes of using the connector and cable when connector connected 110 5 3 DIN rail Mounting Mounting procedures 1 Pull down the mounting bracket at the bottom ...

Page 6: ...sistance between the three lead wires To avoid noise induction keep input signal wire away from instrument power line load lines and power lines of other electric equipment If there is electrical noise in the vicinity of the instrument that could affect operation use a noise filter Shorten the distance between the twisted power supply wire pitches to achieve the most effective noise reduction Alwa...

Page 7: ...or the event output option Event connector socket 1 6 Circuit configuration 24 V DC 1 2 3 DI 4 5 6 Load DO1 DO2 Load Attention in connector plug wiring Use the following connector plug as that connected to the event connector Connector plug is sold separately SRVP 01 Front screw type SRVP 02 Side screw type The lead wires use the stranded wire Use the stranded wire from size 0 2 to 2 5 mm2 AWG 24 ...

Page 8: ...Autotuning function Events Number of events 2 points channel Event type Temperature event Deviation high Deviation low Deviation high low Band Process high Process low Heater break alarm Control loop break alarm Burnout Temperature rise completion Heater break alarm HBA function Number of HBA 2 points Setting range 0 0 to 100 0 A 0 0 A OFF Additional function Number of event delay times 1 to 255 t...

Reviews: