background image

 

IMS01P06-E2

 

7

 

Terminal No. 11 is not used.

 

 

Use the solderless terminal appropriate to the screw 
size (M3)

.

 

 
 

6.3 Pin Layout of Connector 

 

PROFIBUS connector 

 

 

PROFIBUS connector 

(COM. PORT) 

 

 

Pin No. 

Signal name 

Symbol

 

Unused

 

Unused

Receive data/transmission data (plus) 

RxD/TxD-P

 

Unused

Signal ground 

DGND 

Termination resistor supply voltage (5 V) 

VP 

 

Unused

Receive data/transmission data (negative) 

RxD/TxD-N

 

Unused

 

The PROFIBUS cable (a connection cable of PLC and 
SRV) is provided by customer. As for the PROFIBUS 
cable, there is a case prepared by a PLC manufacturer.   

 

The details except the above are connected to a home 
page of PROFIBUS International, and obtain necessary 
information. 
URL: http://www.profibus.com/ 

 
 

 

Event connector 

 

This is a connector installed in the V-TIO-G/V-TIO-H module 
only when provided with the event input (option) or the event 
output (option). 
 

 

Event connector   

(socket) 

 

 
 

 

 

Circuit configuration 

 

24 V DC

1

2

3

DI 

4

5

6

Load

DO1

DO2

Load

 

 

 

Attention in connector (plug) wiring 

• 

Use the following connector (plug) as that connected to the 
event connector.   
Connector (plug) is sold separately. 
SRVP-01 (Front-screw type) 
SRVP-02 (Side-screw type) 

• 

The lead wires use the stranded wire. 

• 

Use the stranded wire from size 0.2 to 2.5 mm

2

 (AWG 24-12). 

• 

Stripping length is as follows.

 

SRVP-01: 10 mm 
SRVP-02: 7 mm 

• 

Recommended tightening torque of the lead wire in the 
connector (plug):  0.5 to 0.6 N

m (5 to 6 kgf

cm) 

Screw size:  SRVP-01:  M2.5 
 SRVP-01: 

M3 

 

[SRVP-01] Front-screw type 

[SRVP-02] Side-screw type

Stripping length

10 mm 

Stranded wire size: 
 0.2 

to 

2.5 

mm

 (AWG 

24-12) 

Recommended tightening 
torque:  0.5 to 0.6 N

 

(5 to 6 kgf

cm) 

Stripping length

7 mm 

Stranded wire size: 
 

0.2 to 2.5 mm

 (AWG 

24-12) 

Recommended tightening 
torque:  0.5 to 0.6 N

 

(5 to 6 kgf

cm) 

 

 

 

 

 

Pin 
No. 

Description 

Digital input (DI)  (

Digital input (DI)  (

+


Digital output (DO) 1 
(Relay contact output) 


Digital output (DO) 2 
(Relay contact output) 

Summary of Contents for V-TIO-G

Page 1: ...nals must be enclosed in the instrumentation panel to avoid electric shock by operating personnel All precautions described in this manual should be taken to avoid damage to the instrument or equipment All wiring must be in accordance with local codes and regulations All wiring must be completed before power is turned on to prevent electric shock instrument failure or incorrect action The power mu...

Page 2: ...mon code Thermocouple input Type Code Range Code Range K K02 0 to 400 C KB9 32 to 752 F K04 0 to 800 C KB8 32 to 1472 F K16 200 to 1372 C KB7 328 to 2501 F K09 0 0 to 400 0 C KC2 32 0 to 752 0 F K35 200 0 to 400 0 C KC1 328 0 to 752 0 F J J02 0 to 400 C JC2 32 to 752 F J04 0 to 800 C JC1 32 to 1472 F J15 200 to 1200 C JB9 328 to 2192 F J09 0 0 to 400 0 C JC4 32 0 to 752 0 F J27 200 0 to 400 0 C JC...

Page 3: ... A green lamp turns on RX TX for PROFIBUS communication During data send and receive A green lamp turns on 4 COMMUNICATION SETTING Set communication setting before mounting and wiring of SRV Do not separate the module mainframe from the terminal base with the power turned on If separated adjusted data may be destroyed control be stopped and no return can be made 4 1 Address Setting PROFIBUS addres...

Page 4: ...protocol Modbus Factory set value of the dip switch 1 No 1 OFF No 5 OFF No 2 OFF No 6 OFF No 3 OFF No 7 OFF No 4 OFF No 8 OFF For host communication Modbus see the Module Type Controller SRV Communication Instruction Manual IMS01P01 E 4 3 Host Communication Setting With the dip switch 2 which there is on the right side of module select communication speed for host communication When host communica...

Page 5: ... connector but the same also when not provided with the connector Depth in connector mounting Conduct installation in consideration of the sizes of the connector and cable when connector connected Unit mm Provide space in consideration of the sizes of using the connector and cable when connector connected 110 5 3 DIN rail Mounting Mounting procedures 1 Pull down the mounting bracket at the bottom ...

Page 6: ...sistance between the three lead wires To avoid noise induction keep input signal wire away from instrument power line load lines and power lines of other electric equipment If there is electrical noise in the vicinity of the instrument that could affect operation use a noise filter Shorten the distance between the twisted power supply wire pitches to achieve the most effective noise reduction Alwa...

Page 7: ...or the event output option Event connector socket 1 6 Circuit configuration 24 V DC 1 2 3 DI 4 5 6 Load DO1 DO2 Load Attention in connector plug wiring Use the following connector plug as that connected to the event connector Connector plug is sold separately SRVP 01 Front screw type SRVP 02 Side screw type The lead wires use the stranded wire Use the stranded wire from size 0 2 to 2 5 mm2 AWG 24 ...

Page 8: ...Autotuning function Events Number of events 2 points channel Event type Temperature event Deviation high Deviation low Deviation high low Band Process high Process low Heater break alarm Control loop break alarm Burnout Temperature rise completion Heater break alarm HBA function Number of HBA 2 points Setting range 0 0 to 100 0 A 0 0 A OFF Additional function Number of event delay times 1 to 255 t...

Reviews: