IMS01P06-E2
7
Terminal No. 11 is not used.
Use the solderless terminal appropriate to the screw
size (M3)
.
6.3 Pin Layout of Connector
PROFIBUS connector
PROFIBUS connector
(COM. PORT)
1
5
6
9
Pin No.
Signal name
Symbol
1
Unused
2
Unused
3
Receive data/transmission data (plus)
RxD/TxD-P
4
Unused
5
Signal ground
DGND
6
Termination resistor supply voltage (5 V)
VP
7
Unused
8
Receive data/transmission data (negative)
RxD/TxD-N
9
Unused
The PROFIBUS cable (a connection cable of PLC and
SRV) is provided by customer. As for the PROFIBUS
cable, there is a case prepared by a PLC manufacturer.
The details except the above are connected to a home
page of PROFIBUS International, and obtain necessary
information.
URL: http://www.profibus.com/
Event connector
This is a connector installed in the V-TIO-G/V-TIO-H module
only when provided with the event input (option) or the event
output (option).
Event connector
(socket)
1
6
Circuit configuration
24 V DC
1
2
3
DI
4
5
6
Load
DO1
DO2
Load
Attention in connector (plug) wiring
•
Use the following connector (plug) as that connected to the
event connector.
Connector (plug) is sold separately.
SRVP-01 (Front-screw type)
SRVP-02 (Side-screw type)
•
The lead wires use the stranded wire.
•
Use the stranded wire from size 0.2 to 2.5 mm
2
(AWG 24-12).
•
Stripping length is as follows.
SRVP-01: 10 mm
SRVP-02: 7 mm
•
Recommended tightening torque of the lead wire in the
connector (plug): 0.5 to 0.6 N
⋅
m (5 to 6 kgf
⋅
cm)
Screw size: SRVP-01: M2.5
SRVP-01:
M3
[SRVP-01] Front-screw type
[SRVP-02] Side-screw type
Stripping length
10 mm
Stranded wire size:
0.2
to
2.5
mm
2
(AWG
24-12)
Recommended tightening
torque: 0.5 to 0.6 N
⋅
m
(5 to 6 kgf
⋅
cm)
Stripping length
7 mm
Stranded wire size:
0.2 to 2.5 mm
2
(AWG
24-12)
Recommended tightening
torque: 0.5 to 0.6 N
⋅
m
(5 to 6 kgf
⋅
cm)
Pin
No.
Description
1
Digital input (DI) (
−
)
2
Digital input (DI) (
+
)
3
4
Digital output (DO) 1
(Relay contact output)
5
6
Digital output (DO) 2
(Relay contact output)