7. SPECIFICATIONS 

 

Inputs 

Number of inputs: 

2 points 

Isolated between each channel: 

Thermocouple input, Voltage (low) input 

Not isolated between each channel: 

RTD input, Voltage (high) input,   
Current input 

Input type: 

 Thermocouple 

K, J, T, S, R, E, B, N (JIS-C1602-1995) 

  

PLII 

(NBS) 

  

W5Re/W26Re 

(ASTM-E988-96) 

 RTD: 

Pt100 (JIS-C1604-1997) 

   

JPt100 (JIS-C1604-1989, Pt100 of   

  

 

JIS-C1604-1981) 

 Voltage (low): 

0 to 100 mV 

 Voltage (high): 

0 to 5 V, 0 to 10 V, 1 to 5 V 

 Current: 

0 to 20 mA, 4 to 20 mA 

Sampling cycle: 

500 ms 

PV bias: 

Input span to 

+

Input span 

CT input: 

2 points 
 

0.0 to 30.0 A (CTL-6P-N) or 

 

0.0 to 100.0 A (CTL-12-S56-10L-N) 

 

 

Outputs 

Number of outputs: 

2 points   
(Isolated between input and output, and 
between output and power supply) 

Output type: 

Relay contact: 

250 V AC, 3 A (Resistive load)   

 1a 

contact 

 

Electrical life 300,000 times or more   

 (Rated 

load) 

Voltage pulse: 

0/12 V DC   

 

(Load resistance 600 

 or more) 

Current: 

0 to 20 mA DC, 4 to 20 mA DC 

 

(Load resistance 600 

 or less) 

Voltage: 

0 to 5 V DC, 0 to 10 V DC, 1 to 5 V DC 

 

(Load resistance 1 k

 or more) 

 

 

Control action 

Number of controls: 

2 points 

Control method: 

Brilliant PID control 

Reverse action or direct action is 

selectable (Specify when ordering) 
Heat/cool control is selectable   

(Specify when ordering) 

Additional function: 

Autotuning function 

 

 

Events 

Number of events: 

2 points/channel 

Event type: 

Temperature event: 
 

Deviation high, Deviation low, 

 

Deviation high/low, Band,   

 

Process high, Process low 

Heater break alarm,   

Control loop break alarm,   

Burnout, Temperature rise completion 

 

 

Heater break alarm (HBA) function 

Number of HBA: 

2 points 

Setting range: 

0.0 to 100.0 A (0.0 A: OFF) 

Additional function: 

Number of event delay times: 
 

1 to 255 times 

 

 

Control loop break alarm (LBA) function 

Number of LBA: 

2 points 

LBA time: 

1 to 7200 seconds 

LBA deadband (LBD) setting: 

0 to Input span 

 

 

 

 

Option 

 

Event input 

Number of inputs: 

1 point 

Input type: 

Dry contact input 

Input voltage: 

24 V DC (Rated) 

Input current: 

Approx. 6 mA 

Input details: 

Control RUN/STOP,   

Event interlock release   

(Specify when ordering) 

 

Event output 

Number of outputs: 

2 points 

Output type: 

Relay contact output 

250 V AC, 1 A (Resistive load) 

1a contact 
Electrical life 300,000 times or more   

(Rated load) 

Output details: 

Temperature event, Heater break alarm, 
Control loop break alarm, Burnout, 

Temperature rise completion 

(Specify when ordering) 

 

 

Communications 

Communication interface: 
 

Based on RS-485, EIA standard

 

Communication protocol: 
 PROFIBUS: 

PROFIBUS-DP 

 

Internal communication:  Modbus RTU 

 

Host communication: 

Modbus RTU

 

 

 

Others 

Power supply voltage:  24 V DC

 

Power supply voltage range: 

21.6 V DC to 26.4 V DC

 

Current consumption:  With event input/output (option): 

 

220 mA max./module 

Without event input/output (option): 
 

190 mA max./module 

Allowable ambient temperature range: 

10 to 

+

50 

°

Allowable ambient humidity range: 

5 to 95 %RH (Non condensing) 
Absolute humidity:   
MAX.W.C 29 g/m

3

 dry air at 101.3 kPa 

Weight: 

With event input/output (option): 
 

Approx. 265 g 

Without event input/output (option): 
 

Approx. 255 g 

 

 

Standard 

Safety standard:  UL:  UL61010A-1 

CSA: CAN/CSA-C22.2

 

No1010.1 

CE marking: 

Low voltage directive:  EN61010-1 
EMC directive: 

EN55011, EN61326-1 

C-Tick: 

AS/NZS 2064 (equivalent to EN55011) 

 

Summary of Contents for V-TIO-G

Page 1: ...nals must be enclosed in the instrumentation panel to avoid electric shock by operating personnel All precautions described in this manual should be taken to avoid damage to the instrument or equipment All wiring must be in accordance with local codes and regulations All wiring must be completed before power is turned on to prevent electric shock instrument failure or incorrect action The power mu...

Page 2: ...mon code Thermocouple input Type Code Range Code Range K K02 0 to 400 C KB9 32 to 752 F K04 0 to 800 C KB8 32 to 1472 F K16 200 to 1372 C KB7 328 to 2501 F K09 0 0 to 400 0 C KC2 32 0 to 752 0 F K35 200 0 to 400 0 C KC1 328 0 to 752 0 F J J02 0 to 400 C JC2 32 to 752 F J04 0 to 800 C JC1 32 to 1472 F J15 200 to 1200 C JB9 328 to 2192 F J09 0 0 to 400 0 C JC4 32 0 to 752 0 F J27 200 0 to 400 0 C JC...

Page 3: ... A green lamp turns on RX TX for PROFIBUS communication During data send and receive A green lamp turns on 4 COMMUNICATION SETTING Set communication setting before mounting and wiring of SRV Do not separate the module mainframe from the terminal base with the power turned on If separated adjusted data may be destroyed control be stopped and no return can be made 4 1 Address Setting PROFIBUS addres...

Page 4: ...protocol Modbus Factory set value of the dip switch 1 No 1 OFF No 5 OFF No 2 OFF No 6 OFF No 3 OFF No 7 OFF No 4 OFF No 8 OFF For host communication Modbus see the Module Type Controller SRV Communication Instruction Manual IMS01P01 E 4 3 Host Communication Setting With the dip switch 2 which there is on the right side of module select communication speed for host communication When host communica...

Page 5: ... connector but the same also when not provided with the connector Depth in connector mounting Conduct installation in consideration of the sizes of the connector and cable when connector connected Unit mm Provide space in consideration of the sizes of using the connector and cable when connector connected 110 5 3 DIN rail Mounting Mounting procedures 1 Pull down the mounting bracket at the bottom ...

Page 6: ...sistance between the three lead wires To avoid noise induction keep input signal wire away from instrument power line load lines and power lines of other electric equipment If there is electrical noise in the vicinity of the instrument that could affect operation use a noise filter Shorten the distance between the twisted power supply wire pitches to achieve the most effective noise reduction Alwa...

Page 7: ...or the event output option Event connector socket 1 6 Circuit configuration 24 V DC 1 2 3 DI 4 5 6 Load DO1 DO2 Load Attention in connector plug wiring Use the following connector plug as that connected to the event connector Connector plug is sold separately SRVP 01 Front screw type SRVP 02 Side screw type The lead wires use the stranded wire Use the stranded wire from size 0 2 to 2 5 mm2 AWG 24 ...

Page 8: ...Autotuning function Events Number of events 2 points channel Event type Temperature event Deviation high Deviation low Deviation high low Band Process high Process low Heater break alarm Control loop break alarm Burnout Temperature rise completion Heater break alarm HBA function Number of HBA 2 points Setting range 0 0 to 100 0 A 0 0 A OFF Additional function Number of event delay times 1 to 255 t...

Reviews: