4 • 35-3001-01 Combustible Gas Sample-Draw Detector
Detector/Amp Terminal Strip
The detector/amp terminal strip is the upper twelve-point terminal strip in the bottom right corner
of the main circuit board. Use the detector/amp terminal strip to connect the combustible gas sensor
to the main circuit board.
NOTE:
The combustible gas sensor is factory-wired to the main circuit board. See the
“Installation” section on page 6 for all wiring procedures related to the sample-draw
detector.
Interconnect Terminal Strip
The interconnect terminal strip is the lower twelve-point terminal strip in the bottom right corner of
the main circuit board. Use the interconnect terminal strip to connect the sample-draw detector to a
controller.
Oxygen Sensor Terminal Strip
The oxygen sensor terminal strip is a two-point terminal strip in the upper right corner of the main
circuit board. This terminal strip is not used in this version of the sample-draw detector.
Pump Connector
The pump connector is the two-point connector below the oxygen terminal strip in the upper right
corner of the main circuit board. Use the pump connector to connect the pump to the main circuit
board.
NOTE:
The pump is factory-wired to the main circuit board. See “Installation” on page 6 for all
wiring procedures related to the sample-draw detector.
Flowmeter Circuit Board Connector
The flowmeter circuit board connector is a six-position connector in the upper left corner of the
main circuit board. Use the flowmeter circuit board connector to connect the flowmeter circuit
board to the main circuit board.
NOTE:
The flowmeter circuit board is factory wired to the main circuit board. See “Installation”
on page 6 for all wiring procedures related to the sample-draw detector.
Flowmeter Circuit Board
The flowmeter circuit board is mounted to the left side of the main circuit board using standoffs. It
includes the flowmeter, sensor flow control valve, status LEDs, pressure switch, and pump reset
switch.
Flowmeter
The flowmeter is mounted to the right side of the flowmeter circuit board. You can see it through
the window in the door. A ball in the flowmeter column indicates the flow rate to the sensor. The
flowmeter measures the flow in the range 0.2 to 2.0 SCFH (Standard Cubic Feet per Hour). The
optimum flow rate is 1.0 SCFH.
Sensor Flow Control Valve
The sensor flow control valve is mounted to the flowmeter circuit board above the flowmeter. The
sensor flow control valve adjusts the flow rate to the detector. Turn the valve’s knob
counterclockwise to increase the flow and clockwise to decrease the flow.