35-3010A-13 Sample-Draw Detector • 5
Overview
This manual describes the 35-3010A-13 sample-draw detector. This manual also describes how to
install, start up, maintain, and calibrate the detector. A parts list at the end of this manual lists
replacement parts and accessories for the sample-draw detector.
Specifications
Table 1 lists specifications for the 35-3010A-13.
WARNING: When using the 35-3010A-13, you must follow the instructions and warnings in this
manual to assure proper and safe operation of the 35-3010A-13 and to minimize the
risk of personal injury. Be sure to maintain and periodically calibrate the 35-3010A-
13 as described in this manual.
Table 1: Specifications
Target Gases & Detection
Ranges
Hydrogen (H
2
): 0 - 10% volume
Oxygen: 0-25% volume
Input Power
24 VDC
Current Draw
240 mA
Output Signals
4-20 mA each channel
Construction (housing)
Fiberglass/polyester (NEMA 4X)
Dimensions
15.44 in. H x 12.55 in. W x 8.31 in. D
Weight
14 lbs.
Sampling Method
Sample-draw
Sample Flow
1.2 SCFH (nominal)
Response Time
90% in 30 seconds
Accuracy
Hydrogen:
± 5% of reading or ± 2% of full scale (whichever is greater)
Oxygen:
± 0.5% O
2