61-1020/61-0230 Molecular Property Spectrometer
Installation
This section describes procedures to mount the combustible gas detector in the monitoring
environment and wire it to a controller.
If you purchased a 61-0230 detector that is factory installed and wired to a controller, detector
installation is not necessary, but the detector wiring can be confirmed as described in “Wiring the
Combustible Gas Detector to a Controller” on page 9.
Mounting the Combustible Gas Detector
1. Select a mounting site that is representative of the monitoring environment. Consider the
following when selecting the mounting site:
• Select a site where the detector is not likely to be bumped or disturbed. Make sure there is
sufficient room to perform start-up, maintenance, and calibration procedures.
• Select a site where the target gas is likely to be found first. For lighter gases, mount the
detector near the ceiling. For heavier gases, mount the detector near the floor.
Figure 2: Mounting the Combustible Gas Detector
2. At the selected mounting site, hang or mount the junction box with the detector facing down
(see Figure 2).
2.70
.38
J-Box
3/4 NPT
Female
Rubber
Spacers,
3X
.75
3.65
MPS LEL Detector
7.10 MAX