61-1001RKSS Hydrogen Detector • 1
Overview
This manual describes the 61-1001RKSS hydrogen detector (internal amplifier type). This
manual also describes how to install, start up, maintain, and calibrate the detector when it
is used with a gas monitoring controller. A parts list at the end of this manual lists
replacement parts and accessories for the hydrogen detector.
Specifications
WARNING: Do not use this product in a manner not specified in this instruction
manual.
Table 1 lists specifications for the hydrogen detector.
WARNING: When using the 61-1001RKSS, you must follow the instructions and
warnings in this manual to assure proper and safe operation of the
61-1001RKSS and to minimize the risk of personal injury. Be sure to
maintain and periodically calibrate the 61-1001RKSS as described in this
manual.
Table 1: 61-1001RKSS Specifications
Description
Specifications
Target Gas
Hydrogen
Area Classification
Explosion proof for Class I, Groups B, C, and D
Sampling Method
Diffusion
Detection Range
0 to 100 %LEL
Response Time
90% in 45 seconds
Accuracy
± 5% of reading or ± 2% LEL (whichever is greater)