65-2662XL-04 M2A-XL Transmitter
Chapter 5: Configuration Mode
•
33
4. When you have scrolled through all the adjustable parameters,
SAVE IT? YES/NO
appears
on the display.
5. If you do not wish to save the adjustments and want to exit Configuration Mode, press and
release the DOWN/NO button. The
DO OVER? YES/NO
message will display. Press and
release the DOWN/NO button. The
ABORT? YES/NO
message will display. Press the UP/
YES button to return to normal operation.
If you wish to change some of the adjustments made, press and release the DOWN/NO
button. The
DO OVER? YES/NO
message will display. Press and release the UP/YES
button. The
Re-do Config
message will display and the M2A-XL will return to the first
adjustable parameter. Go back to step 3 and continue.
If you wish to save the adjustments made, press and release the UP/YES button.
Config
Saved
is indicated on the display for a few seconds and the M2A-XL returns to normal
operation.
A2 OffDy (alarm 2 off
delay)
(0 sec.)
The amount of time the M2A-XL delays turning off the alarm 2 circuit
once an alarm 2 condition passes. This parameter appears only if the
alarm 2 relay reset setting is set to
SELF-RST
. It can be set in 1 sec
-
ond increments from 0 - 60 seconds, in 1 minute increments from 1 -
15 minutes, and in 15 minute increments from 15 - 60 minutes.
ZeroSupp
(2 ppm)
The zero suppression feature helps prevent “jumpy” readings near the
fresh air reading.
For example, if the zero suppression is
2.0 ppm,
the M2A-XL will dis
-
play a reading of 0 ppm for gas readings from -2 ppm to 2 ppm. It is
settable from 0 to 6% of the detection range.
FILTER
(5 secs)
The filter feature helps “smooth out” jumpy or noisy signals from the
detector. You can set the filter from 0 seconds to 60 seconds in 5 sec
-
onds increments.
The displayed gas reading is the average reading over the previous
time period defined by the filter setting. So if the filter is set to 5 sec
-
onds, the displayed gas reading is the average over the past 5 seconds.
CAL Time
(15 mins)
The calibration time-out sets the amount of time after the last button
push while in Calibration Mode that the M2A-XL will wait before
returning to normal operation. If the calibration time-out is set to
15
mins
, then M2A-XL will return to normal operation automatically 15
minutes after the last button push.
Auto Zero
(Enabled)
If set to
Enabled
, the M2A-XL’s firmware will monitor the zero (fresh
air) reading and make automatic zero adjustments under precisely
specified conditions if it determines that a reading change is due to
normal sensor drift.
If set to
Disabled
, the Auto Zero function is turned off.
Table 5: Configuration Parameters (Continued)
Parameter
(Factory Set Value)
Description