48 • Display Mode
EAGLE 2 Operator’s Manual
4. Press and release the AIR
▲
YES button to scroll through screens that display the rest
of the active channels’ alarm settings.
Select User ID Screen
This screen displays only if USER/STATION ID in the Setup Mode menu is set to ON (see
“Turning the User/Station ID Function On or Off” on page 109). Use this screen to select a
user ID from the user ID list in the EAGLE 2’s memory. The current user ID is displayed.
A user ID can be up to 16 characters long. The EAGLE 2 can store up to 32 user IDs.
The user ID provides a way to identify the EAGLE 2 user during a data logging session. If
the user ID is changed during an operating session, a new data session is initiated with the
new user ID attached to it. This allows you to change the user ID during operation and
have each user ID that was used during an operating session saved for the corresponding
data. See the Eagle 2 Data Logger Management Program Operator’s Manual for a detailed
description of data logging and the user ID.
The user ID list cannot be edited using the EAGLE 2 user interface. The Eagle 2
Maintenance Data Loader Program is required to define or change user IDs in the user ID
list. For a detailed description of editing the list of user IDs stored in the EAGLE 2, see the
Eagle 2 Maintenance Data Loader Program Operator’s Manual.
CHANNEL 2
OXY 0- 40.0 vol%
LO ALRM: 19.5 vol%
HI ALRM: 23.5 vol%
CHANNEL 3
H2S 0-100.0 ppm
LO ALRM: 5.0 ppm
HI ALRM: 30.0 ppm
STEL ALRM: 5.0 ppm
TWA ALRM: 1.0 ppm
CHANNEL 1
CH4 0- 100 %LEL
LO ALRM: 10 %LEL
HI ALRM: 50 %LEL
LO ALRM: 5000 ppm
HI ALRM:25000 ppm
CHANNEL 4
CO 0- 500 ppm
LO ALRM: 25 ppm
HI ALRM: 50 ppm
STEL ALRM: 200 ppm
TWA ALRM: 25 ppm
AIR
YES
AIR
YES
AIR
YES
AIR
YES
SELECT
USER ID?
CURRENT USER ID
JOHN
www.
.com
information@itm.com