M2A Transmitter Operator’s Manual
Chapter 2: Description
Overview
This chapter describes external and internal components of the M2A Transmitter.
External Description
This section describes the junction box and all external components of the M2A transmitter.
Figure 1: M2A External Components
Junction Box
The M2A’s cast aluminum junction box is dust and weather resistant. The junction box also protects the M2A
and all connections made to it. Use the three 3/4 NPT conduit ports to mount the detector to the junction box
(factory installed in the bottom port) and connect wiring from an external device (left port). The top port is
shipped with a factory installed and sealed conduit plug to avoid leaks into the junction box. If necessary, the
conduit plug can be removed and the top port can be used for wiring.
WARNING:
If the top conduit port is used for wiring, be sure to seal the threads to ensure water does not
enter the junction box. See “Wiring the M2A Transmitter” on page 28 for complete wiring
instructions.
Use the junction box’s two mounting holes to mount the M2A to a vertical surface at the monitoring site. The
window in the cover on the front of the junction box allows you to view the OLED display and use the magnetic
wand to actuate the magnetic control switches so you can perform non-intrusive calibration. Removing the cover
Magnetic
W and
Junction Box Cover
3/4 NPT Conduit Port, Plugged
3/4 NPT
Conduit Port
W indow
Mounting Slot (2x)
Detector
(Catalytic LEL Detector Shown)