40
M2A Transmitter Operator’s Manual
NOTE:
If the ENTER button is pressed while the M2A is in an alarm 2 condition, the A2 LED will flash but
all other indications will remain unchanged.
You cannot de-energize the alarm 2 relay until the gas reading falls below the alarm 2 setpoint.
Fail Condition
Fail Condition Indications
The M2A indicates a fail condition for any of the following:
•
The detector wiring is disconnected or incorrectly connected.
•
The plug-in sensor is not properly plugged into the socket in the detector housing body.
NOTE:
It could take up to 40 minutes for a disconnected CT-7 style NH
3
plug-in sensor to trigger a fail
condition.
•
The display reading is -10% of full scale or lower.
When the M2A senses a fail condition, it alerts you as follows:
•
The F LED turns on.
•
The gas reading is replaced by the
FAIL
message.
•
The fail relay de-energizes.
NOTE:
The fail alarm has a 30 second delay.
Responding to a Fail Condition
1. Verify that the detector wiring is correctly and securely connected.
2. If the M2A has a replaceable plug-in sensor, verify that the replaceable plug-in sensor in the detector
housing is properly installed.
Low Power Alarm
Low Power Alarm Indications
The M2A senses a low power condition when the DC power source is 9.5 volts or less.
WARNING:
While in a low power condition, the M2A is not an active gas monitor.
When the M2A senses a low power condition, it alerts you as follows:
•
The F LED turns on.
•
The message
LowPower
is indicated on the top line of the OLED display and the input voltage is displayed
on the bottom line of the OLED display.
•
The fail relay de-energizes.
NOTE:
The low power alarm cannot be cleared using the ENTER button.
When the voltage increases to 10.0 volts, the low power alarm is cleared and the M2A will begin its warm-up
sequence.