14 • Sample Draw Combustible Gas Detector

Replacing Components of the Combustible Gas
Sample Draw Detector

This section includes procedures to replace the sensor, filter, and ferrules.

Replacing the combustible gas sensor

1. Turn off incomming power.

2. Open the housing door of the sample draw detector.
3. Unscrew and remove the two screws that secure the retraining plate, then lift the 

plate, connector, and sensor out of the housing.

4. Unplug the connector from the sensor.
5. Verify that you are using the correct replacement sensor (NC-6240 is printed on the 

sensor), then plug the sensor into the connector.

6. Place the sensor in the combustible gas sensor cavity, then position the retaining plate 

on the two standoffs.

7. Secure the retaining plate to the standoffs with the two screws you removed in step 3.
8. Turn on incomming power.

CAUTION: Allow the replacement sensor to warm up for 15 minutes before you continue.

9. Calibrate the replacement sensor as described in the “Calibration” section on page 16.

Replacing the filter

1. Open the housing door of the sample draw detector.

2. Note the direction of the arrow on the filter. The arrow indicates the direction of the 

sample flow.

3. Disconnect the filter from the elbows on each end of the filter, then remove the filter 

from the sample draw detector.

4. Make sure the arrow is pointing in the same direction as the arrow on the filter you 

removed, then connect each end of the replacement filter to the elbows.

5. Verify that the flow rate is approximately 1.5 SCFH, then close the housing door.

Replacing the ferrules

The INLET and EXHAUST fittings each includes two ferrules that seal the incoming or 
exhaust tubing to the fitting. Replace the ferrules if the seal is bad or if you replace the 
sample tubing. Always replace the ferrules as a pair.

1. Disconnect the sample tubing from the fitting, then unscrew the nut from the fitting.

2. Verify that the ferrules did not remain in the nut. If necessary, remove the ferrules 

from the nut.

3. Position the nut so the threaded end is facing you, then insert the bottom (smaller) 

ferrule into the nut. Insert the ferrule so the flat side is facing down.

NOTE: Make sure the bottom ferrule is laying flat in the nut.

4. Insert the cone-shaped front ferrule on top of the bottom ferrule. Insert the ferrule so 

the smaller end of the cone is facing up.

5. Screw the nut onto the fitting, then connect the sample tubing to the fitting. Make sure 

you firmly tighten the nut with a wrench.

Summary of Contents for 35-3000RKA-LEL

Page 1: ...detector Table 1 Specifications Target Gas Combustible Gas Input Power 24 VDC Construction housing Fiberglass polyester NEMA 4X Dimensions 8 5 in H x 6 5 in W x 4 25 in D Weight 4 5 lbs Sampling Meth...

Page 2: ...re attached to the back of the housing one at each corner Use the mounting feet to install the housing to a vertical surface Use the two conduit hubs on the bottom of the housing to make wiring connec...

Page 3: ...d or clogged Pump The pump is behind the main circuit board near the top of the sample draw detector The pump pulls the gas sample into the sample draw detector The pump operates on 24 VAC which is ge...

Page 4: ...he EXHAUST fitting accepts 1 4 in rigid tubing See the Installation section on page 7 to connect tubing to the EXHAUST fitting Detection System The detection system consists of the combustible gas sen...

Page 5: ...f the transmitter The transmitter is factory wired to the sensor and main circuit board Test points The test points are located on the left side of the transmitter and are labeled TP and TP A 100 mV 5...

Page 6: ...sure switch are factory wired to the circuit board See the Installation on page 7 for all wiring procedures related to the sample draw detector Relay The relay is to the left of the detector terminal...

Page 7: ...ider the following when you select the mounting site Is there enough room to open the housing door and make wiring connections at the bottom of the housing and tubing connections at the right of the h...

Page 8: ...to seal the connection between the tubing and the INLET fitting See Appendix A Parts List for an example of an appropriate metal insert 2 Place the opposite end of the tubing at the sampling area CAUT...

Page 9: ...e Gas Detector 4 20 Feedback Ground WHT GR N BLK GN D 2 4 V _ LEL O2 AM P P AM P 4 2 0 GREEN BLA C K WH ITE RED PUMP ASSY INTERNALLY WIRED 24VDC GND 24V 4 20 RD PUM P PSW TP TP ZERO SPAN GND 24V 4 20...

Page 10: ...of the sample line with your thumb If the flowmeter ball drops to the bottom of the flowmeter the incoming sample line is not leaking 7 Remove your thumb from the sample line verify the flowmeter retu...

Page 11: ...e target gas Preparing for the response test NOTE This procedure describes the RKI calibration kit that includes a gas collection bag A calibration kit that uses a demand flow regulator is also availa...

Page 12: ...ems you may encounter with the sample draw combustible gas detector NOTE This troubleshooting guide describes sample draw detector problems only See the instruction manual for monitoring device if it...

Page 13: ...pump etc The sample draw detector is malfunctioning The demand flow regulator is not operating properly if one is used for calibration instead of a gas bag Recommended action 1 Verify that the calibra...

Page 14: ...row indicates the direction of the sample flow 3 Disconnect the filter from the elbows on each end of the filter then remove the filter from the sample draw detector 4 Make sure the arrow is pointing...

Page 15: ...low to 0 6 SCFH 2 Slowly turn the low flow potentiometer counterclockwise just until the sample draw detector goes into low flow alarm NOTE The low flow potentiometer is accessible through a circular...

Page 16: ...the correct test points output for the calibrating sample Output mV calibrating sample fullscale X 400 100 For example with a calibrating sample of 50 LEL and a fullscale setting of 100 LEL the corre...

Page 17: ...e sample tubing from the inlet line then close the clamp Setting the Response Reading 1 Connect the sample tubing from the gas collection bag to the fixed flow regulator then open the clamp 2 Screw th...

Page 18: ...Filter Boston DFU9933 05 DQ 57 1050RK Transmitter specify target gas when ordering 61 0145RK Combustible gas sensor NC 6240 plug in type LEL range 81 0002RK 01 Calibration cylinder 50 LEL Hydrogen 34...

Reviews: