14 • 61-1000RK-05/61-0140RK-05 Combustible Gas Detector
Setting the Zero Reading
CAUTION:
If you suspect the monitoring environment is not free of combustible vapors, use the
calibration kit and a zero air calibration cylinder to introduce “fresh air” to the
detector and verify an accurate zero setting.
1.
Verify that the detector is in a fresh air environment.
2.
Follow the directions in the controller’s operator’s manual for setting the zero
reading.
Setting the Response Reading
1.
Follow the directions in the controller’s operator’s manual for setting the response
reading (span).
2.
When the directions call for exposing the detector to gas, turn the regulator’s on/off
knob counterclockwise to open it.
3.
Allow the gas to flow for one minute before continuing with the directions.
4.
After setting the response reading, turn the regulator’s on/off knob clockwise to close
it.
5.
Unscrew the regulator from the cylinder.
Returning to Normal Operation
1.
Unscrew the calibration cup from the detector.
NOTE:
For convenience, leave regulator and calibration cup connected by the sample
tubing.
2.
When the controller display reading falls below the alarm points, return the controller
to normal operation.
NOTE
: If you do not allow the gas reading to decrease below the alarm points, then
unwanted alarms may occur.
3.
Verify that the controller display reading decreases and stabilizes at 0 %LEL.
4.
Store the components of the calibration kit in a safe and convenient place.