3.3
Single Shot, Lockout ON, Live Line Out, Block Instantaneous after 1
st
Trip
With the switch setting depicted above the relay will go through the following operations.
1. Once the breaker has tripped and the Protection trip contact has closed the A/R in
progress LED will flash and the A/R contact will close. The relay will wait for the setting of
Dead Time 1 to expire, it will then issue a reclose output pulse, the counter will increment
one count and the A/R in progress LED will become steady.
2. If the Protection Trip Contact is still closed after the reclose pulse, the Block Instantaneous
Protection contact will open, the LED will extinguish and the relay will go directly to Lockout.
3. If the Protection Trip Contact has opened the relay will wait for the Reclaim Time to expire
before removing the Block Instantaneous Protection contact and LED and driving to
Lockout.
4. The Lockout indication and contact has to be reset from the front panel of the relay.
5. Refer to flowchart 1B230B-3-100